Zigzag polarity verification starts with each winding section’s limb, terminal direction and series junction. Those details determine whether the intended zero-sequence ampere-turns cancel. A signed section map exposes a reversal that a continuity check can miss. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
The relevant cancellation concerns the ampere-turns produced by equal zero-sequence currents. It does not mean that the transformer has no core flux during normal energization. The SEL grounding paper describes opposing coils from different phases on each magnetic core; that distinction provides the starting point for a signed winding map.

Give every section a limb and a direction
Consider an illustrative symmetrical winding with six sections of N turns each. Define phase currents IA, IB and IC as flowing from their line terminals toward the neutral. Use a plus sign for a section’s magnetomotive force in the chosen positive direction around its limb, and a minus sign for the opposite direction. The following map describes one internally consistent connection convention.
| Series phase path | First section contribution | Second section contribution |
|---|---|---|
| A to neutral | +NIA on limb A | −NIA on limb B |
| B to neutral | +NIB on limb B | −NIB on limb C |
| C to neutral | +NIC on limb C | −NIC on limb A |
Each current passes through two sections in series. Their location on different limbs does not divide that current. Dot markings, start/finish labels and the actual lead arrangement must establish these signs; a photograph showing two coils per limb is insufficient.
Apply the zero-sequence current vector
The limb magnetomotive forces are FA = N(IA − IC), FB = N(IB − IA) and FC = N(IC − IB). Currents are in amperes, N is a turn count and each F is in ampere-turns. For pure zero sequence, IA = IB = IC = I0, including phasor angle. All three limb balances then vanish in this ideal equal-turn model.
Meanwhile, the neutral current is IN = IA + IB + IC = 3I0 with the chosen reference directions. The neutral carries the sum of three phase paths. Six physical sections do not create six independently supplied paths.
During normal balanced positive-sequence operation, the phase currents are separated by 120 degrees. Their differences need not vanish. The core retains its normal excitation, and leakage fields and winding resistance also remain present during zero-sequence duty. Ampere-turn cancellation therefore explains a low zero-sequence impedance mechanism without proving zero impedance or unlimited fault capacity.
Expose a reversed section before accepting the map
If the C-path section on limb A were reversed, its contribution would become +NIC. Limb A would then have N(IA + IC), or 2NI0 under pure zero sequence. That is a direct contradiction of the intended cancellation. A one-turn difference instead leaves a residual proportional to that turn error and I0; it is a smaller defect with the same diagnostic logic.
Reconcile the signed map with low-energy polarity and connection tests under the approved arrangement. Trace any measured limb imbalance to its section and series junction, then verify the corrected connection.
Distinguish a reversal from a turn error
Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].
Assume 100 turns per section and 50 A RMS equal zero-sequence phase currents. Correct opposing sections give 100 × 50 − 100 × 50 = 0 A·turn. Reversing one section gives 10,000 A·turn; a one-turn excess gives 50 A·turn. Both require correction, but their magnetic consequences differ by a factor of 200 in this linear ampere-turn comparison.
References
- D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
- IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.

