  • Chenfan Power

In a conventional zigzag connection, each line-to-neutral path contains two winding sections in series. Both sections carry the same path current. Start the balance calculation from that connection map, including any additional branch, tap or fault path in the actual construction. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

There are still important balance questions. Three phase paths may carry unequal current, parallel conductors within a section may share unequally, and sections carrying equal current may have unequal turn counts. These mechanisms cannot be diagnosed by a single total-neutral-current reading.

Checking Current Balance in Zigzag Winding Halves: technical review table
Write continuity before calculating imbalance

Write continuity before calculating imbalance

For an identified A-phase series path, IA1 = IA2 = IA. Apply the same relationship to B and C. In a symmetrical pure zero-sequence condition, IA = IB = IC = I0 and IN = 3I0, using currents referenced toward the neutral. Equal section currents arise from continuity and symmetry; they are not six independent design allocations.

Balance questionControlling relationshipEvidence needed
Two sections in one phase pathSeries current equalityVerified junctions and absence of an unintended branch
A, B and C phase pathsCoupled impedance and applied voltagesThree synchronized phase-current measurements
Opposing sections on one limbSigned turns multiplied by section currentsTurn counts, polarity and section identity
Parallel conductors within a sectionBranch impedance and induced-voltage balanceInternal branch construction and suitable branch evidence

A neutral total can conceal a phase mismatch

As an illustrative resistive circuit only, suppose three paths see the same 10 V RMS and have resistances of 1.00, 1.05 and 0.95 ohm. Their currents are 10.000, 9.524 and 10.526 A. The total is 30.050 A, close to the 30 A expected from three nominal paths, yet individual currents differ visibly. This simple calculation shows why the sum is a weak balance check.

A real zigzag requires mutual inductance and magnetic coupling in addition to those resistances. Use the full coupled circuit to predict operating currents. Winding resistance measurements remain useful for finding inconsistent paths, but they do not independently reproduce the alternating-current current distribution.

For equal section turns N under the chosen zigzag polarity convention, one limb balance is F = N(IA − IC). With 100 illustrative turns and the resistive currents above, that limb has approximately −52.6 ampere-turns. The numerical result describes the illustrative circuit, not a tested transformer.

Separate turn error from current error

If opposing sections have N1 and N2 turns, the limb balance becomes F = N1IA − N2IC. Even equal IA and IC will leave a residual when N1 differs from N2. Conversely, correct turn counts will not eliminate the residual created by unequal phase currents. These two cases can have similar magnetic symptoms and require different construction evidence.

Calculate a phase-current deviation from the complex mean Imean = (IA + IB + IC)/3, preserving both magnitude and angle. Use the actual turn counts to translate that deviation into each limb’s ampere-turn residual. Report the section mapping with the result. Use that map to distinguish phase-current imbalance from a turn-count error in the opposing sections.

Express the hidden imbalance on a common reference

Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].

For the assumed 10 V resistive screen, currents are 10.000, 9.524 and 10.526 A and their mean is 10.0167 A. The maximum magnitude deviation from that mean is 5.09%. With 100 opposing turns, the A-to-C limb residual is −52.63 A·turn. Use synchronized phasors and the coupled winding model for the actual acceptance decision.

References

  1. D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
  2. IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.