Engineering tools
Transformer Quick Electrical Calculator
Fast everyday transformer calculations: rated current, voltage ratio, taps, short-circuit, star/delta, resistance correction and parallel operation.
A free engineering tool from Chenfan Electric. Runs in your browser. No registration required.
- 01Choose a calculatorSeven everyday calculations on one page.
- 02Enter valuesResults update as you type.
- 03Copy or verifyCopy the results or open the calculation details.
How to calculate rated line current
Choose single-phase or three-phase and enter rated apparent power (kVA or MVA) and the HV and LV line voltages (V or kV). With S in VA and U in V, use I = S ÷ (√3 × U) for three-phase or I = S ÷ U for single-phase. The line voltage ratio is the HV line voltage divided by the LV line voltage.
A 1,000 kVA three-phase transformer rated 11/0.4 kV has a rated line current of 52.486 A on the HV side and 1,443.376 A on the LV side. The line voltage ratio is 27.5:1.