Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Twelve-Pulse Groups: Diagnose Unequal Harmonic Cancellation

  • Chenfan Power

The harmonic cancellation associated with a twelve-pulse arrangement assumes the intended relationship between its two six-pulse groups. Unequal currents, impedance differences or phase displacement errors leave residual components. A harmonic spectrum at the common terminal shows the result, but not necessarily its cause. Apply the HVDC transformer specification framework of IEC/IEEE 60076-57-129 to the stated liquid-immersed equipment [1].

Measure or calculate each group before combining them. Refer harmonic phasors through the correct winding ratio and vector connection. Harmonic phase displacement must be derived for that order; applying the fundamental phase shift unchanged to every harmonic is unreliable.

Twelve-Pulse Groups: Diagnose Unequal Harmonic Cancellation: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

Use phasors to test cancellation

For an order expected to cancel, write two referred contributions as I1 = A and I2 = −B exp(jε). Their residual magnitude satisfies |Ir|² = A² + B² − 2AB cos ε. A and B are harmonic RMS amperes; ε is the residual phase error in radians. Equal magnitude and zero error give zero in this ideal pair.

ObservationCandidate mechanismDistinguishing data
Group magnitudes unequal; phase relation closeLoad or impedance asymmetrySeparate group currents and impedances
Magnitudes close; phase relation wrongConnection or phase-shift issueRatio/vector verification and harmonic phasors
Residual varies with operating pointOverlap or control-dependent asymmetryDC load, firing state and valve-side voltage
New unexpected orders appearBroken symmetry in supply or converterPhase unbalance and conduction records

Measure the residual of unequal opposing groups

Assume primary-referred RMS harmonic contributions A = 100 A and B = 90 A, with residual phase error ε = 5°. The residual is √(100² + 90² − 2 × 100 × 90 cos 5°) = 12.98 A. Pure magnitude mismatch gives 10.00 A; equal 100 A contributions with the same angle error give 8.72 A. The combined error exceeds either isolated case. Measure magnitude and phase separately before correcting the winding connection or bridge sharing.

Compare like operating points

Use the same time window and DC operating state for both groups. A current spectrum taken during one group’s load change cannot be compared with a steady spectrum from the other. Preserve phase references; magnitudes alone cannot test cancellation.

Check whether instrument ratios, polarity and timing introduce a false mismatch. Then compare winding-pair impedances and the actual converter control states. Different mechanisms can produce similar total distortion, which is why one THD value is a weak diagnostic.

Calculate each group contribution and the combined residual, then distinguish phase error, amplitude mismatch and the actual operating state. A twelve-pulse designation alone cannot promise a fixed reduction: cancellation belongs to the waveforms and topology used in the calculation.

Include normal converter operation and converter-side faults in the transformer transient study [2].

References

  1. IEC/IEEE, IEC/IEEE 60076-57-129:2017, Power transformers – Part 57-129: Transformers for HVDC applications.
  2. CIGRE WG B4.51, Technical Brochure 609, Study of Converter Transients Imposed on the HVDC Converter Transformers, 2015.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing