Winding Temperature Indicators: Thermal Image versus Direct Measurement

  • Chenfan Power
Chenfan Electric logo
CHENFAN ELECTRIC
Transformer Core Engineering Notes · CF-N259

The label “winding temperature” on an instrument does not necessarily mean a sensor is inside the winding. Some indicators produce a thermal image using liquid temperature and a load-related heating or calculation arrangement. Others display a direct sensing location. Procurement and operating documents should state which method is installed and what its indication represents.

Winding Temperature Indicators: Model vs Measurement: review items, requested evidence and design boundaries.
Chenfan Electric engineering review map. Not measured data, a manufacturing drawing or an acceptance limit; a text version follows below.

Identify the measurement chain

For a thermal-image indicator, document the temperature input, load-related input and the model or compensation arrangement. For a direct system, record the physical sensing location and channel mapping. Do not treat these chains as interchangeable because both displays use degrees Celsius. Their errors, response and failure modes differ, so alarm and cooling-control functions need to be assessed against the actual instrument design.

Connect settings to transformer test evidence

Compensation values should reflect the OEM’s specified winding-temperature relationship and the applicable test basis. A replacement instrument with factory-default settings may not reproduce the previous approved indication. Record the relevant current-transformer ratio, instrument configuration and calibration or functional checks as applicable. Changes to cooling stages or transformer rating should trigger a review of the indication model, not merely a new label on the dial.

Interpret disagreement before changing settings

A thermal-image value and a fibre-optic channel can legitimately differ because they represent different locations or response models. Investigate the operating state, placement and measurement chain before assuming one must be wrong. Never adjust an indicator merely to make two traces coincide without an engineering basis. A comparison is useful when the expected relationship and its uncertainty are defined in advance.

Specify failure behavior and handover records

Clarify how loss of a sensor, load input, auxiliary supply or communication affects the display and its outputs. A frozen plausible value can be harder to recognize than a clear fault indication. The handover package should include final settings, channel descriptions, control functions and test records. The operating team needs to know whether it is seeing a modelled winding quantity or a direct local measurement before using it for decisions.

Design review checklist
Review itemEvidence to requestBoundary to preserve
MethodThermal image or direct installed sensorA winding label does not identify the method
ConfigurationOEM compensation, ratios and test basisFactory defaults may not fit the unit
Use of indicationLocation, dynamics and fault behaviorDo not force unlike measurements to match

References and scope

  1. IEEE C57.165-2024 — Temperature Monitoring of Liquid-Immersed TransformersPublic standard abstract · Temperature-monitoring methods for liquid-immersed transformers and their measurement/model boundaries.
  2. IEEE C57.91-2025 — Loading Mineral-Oil-Immersed Transformers and Step-Voltage RegulatorsPublic standard abstract · Mineral-oil loading, thermal duty and loading beyond nameplate; do not transfer the scope automatically to ester or dry-type equipment.
Public references establish scope and status, not full-clause compliance. Manufacturer material is product-specific; historical references are not current project codes. Review questions are editorial guidance, not quoted acceptance rules.