A mobile transformer’s reconnection interlock must detect incomplete connections, conflicting channels and a voltage mode that does not match the site. Build its state table around those conditions, the actual sensing chain and the response required by the approved design. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Build the state table from actual hazards
Identify the completed physical connections and the evidence needed to distinguish them. Then associate the relevant protection and control permissives with those states. A signal named “mode valid” is useful only when its generating logic and failure behavior are understood.
| State to test | Evidence condition | Expected design-review conclusion |
|---|---|---|
| Completed intended mode | Required independent evidence agrees | Evaluate the corresponding configured permissive |
| Intermediate selector state | No completed circuit identity established | The logic must not invent a completed mode |
| Position channels disagree | One or more indicated identities conflict | The disagreement remains visible and blocks unsupported inference |
| Signal lost or stale | Current physical state is not established by that channel | Do not treat retained last value as current proof |
| Site selection incompatible | Device mode and intended site interface disagree | Compatibility gate must identify the mismatch |
| Wrong configuration mapping | Signals are valid electrically but mapped to another drawing revision | Configuration identity requires correction before relying on the logic |
Test the complete indication chain
Trace sensors, coding, wiring, controller inputs and displayed text. Check open-circuit, short-circuit and stuck-state cases within the qualified test method. Some coding schemes detect one class of failure but allow another to resemble a valid mode. Record exactly which failures the design detects rather than asserting that redundancy handles everything.
Review the interaction with external supply selection and protection settings. The interlock may establish a transformer mode while another system still uses parameters for a different voltage or connection. The complete permissive therefore needs the applicable configuration relationship, not just a local mechanical position.
Keep tests within the approved design
Verify failure-state behavior using the authorized offline or controlled test arrangements. Any test that temporarily changes a signal requires its own approved restoration and verification controls.
After a harness, selector or control-system replacement, recheck the changed mapping and relevant failure cases. A previously successful nominal-state test cannot prove that a new input allocation retains the intended protection against ambiguous states.
For every excluded state, record the input evidence and the resulting logic response. Test that mapping after selector, harness or control changes so the interlock remains tied to the installed power circuit.
Exercise ambiguous selector codes explicitly
Keep protection compensation and transformer connection identity matched across modes [2].
Assume two input bits assign 00 to mode A and 11 to mode B; 01 and 10 are invalid. Only two of four possible codes are valid. A single-bit fault from either valid code becomes invalid, but a common two-bit reversal can mimic the other valid mode. Test common-cause mapping and site compatibility in addition to single-channel failures.
References
- NASA, NASA Systems Engineering Handbook, section 6.5, Configuration Management, official online text.
- B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.