Mobile Transformer Rating with Partly Deployed Radiators

  • Chenfan Power

Partly deployed radiators give a mobile transformer a different thermal configuration. Establish its rating from the connected oil paths, fan airflow, hydraulic restrictions and loss distribution of that arrangement. Record the exact cooler state beside the supported duty. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Mobile Transformer Rating with Partly Deployed Radiators: technical review table
Identify the deployed cooling circuit

Identify the deployed cooling circuit

Record which banks are connected, their physical orientation, the actual fan arrangement and the applicable pump or natural-circulation paths. Distinguish a disconnected bank from a connected bank that is poorly exposed to air. Folded geometry can alter both the external flow and the internal hydraulic boundary.

Deployment conditionBoundary that changesEvidence needed before using a rating
All approved banks deployedReference oil and air pathsThermal evidence for this arrangement and ambient boundary
One bank unavailableParallel hydraulic paths and effective heat-transfer areaValidated partial-deployment configuration
Banks folded or closely spacedAir recirculation and surface exposureEvidence matching the actual deployed geometry
Fan group unavailableAirflow distribution and auxiliary stateSupported degraded-cooling envelope
Temporary connecting pipesPressure drop, elevation and circulation routeActual connection dimensions and flow compatibility

Calculate duty from the complete cooling arrangement

Removing a parallel cooling path changes resistance and the flow division among remaining paths. Air recirculation can make added surface area less effective than its nominal area suggests. Winding hotspots may respond differently from average liquid temperature, especially where the altered flow distribution affects a specific region.

Use applicable pressure-drop and flow evidence to check the assembled liquid circuit. For air cooling, define inlet temperature at the cooler and nearby obstructions rather than relying on a distant ambient reading. A mobile installation can place intake and discharge regions close enough for recirculation to matter.

Connect the configuration to an approved thermal envelope

Request a rating or operating boundary supported for the identified deployment state, with its voltage mode, load, ambient and auxiliary conditions. If the state is not covered, it remains an evidence gap. A field estimate based on the fraction of installed radiators is not an approved derating method.

Include transient duration and starting temperature where a temporary duty is being assessed. A short deployment does not eliminate heat accumulation, and a cool initial bulk temperature does not establish the winding hotspot trajectory.

Pair each deployment state with its approved cooler arrangement, thermal evidence and rating. Resolve changes to banks, fans or piping before assigning the temporary duty.

Screen the loss budget for a partial cooler arrangement

Tie cooling-system condition and operation to the proposed deployed state [2].

Assume a hypothetical partial-cooling state can reject 70 kW at the specified ambient, with 10 kW no-load loss and 80 kW rated load loss at the reference winding temperature. With load loss proportional to K², 10 + 80K² ≤ 70 gives K ≤ 0.866. This preliminary 86.6% load screen still needs hotspot and oil-flow validation for that exact deployment.