Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Transformer Reassembly: Comparing Repeated Thermal Tests

  • Chenfan Power

Compare repeated heat runs through both assembly state and electrical settings. Reassembly may disturb cooling passages, restraints, lead routes or probes. Record the intervention and actual cooling condition using the maintenance evidence [1], then identify which measured temperatures remain comparable.

The comparison must account for the actual assembly and the measurement process. Otherwise assembly sensitivity may be dismissed as scatter, or a sensor relocation may be reported as a design change.

Transformer Reassembly: Comparing Repeated Thermal Tests: technical review table
Pair the build records before pairing the temperatures

Pair the build records before pairing the temperatures

Document the parts disturbed, cooling passages opened, clamping changes and subsequent drying or filling operations. Check for displaced insulation, altered duct alignment and changes to directed-flow paths. Record the liquid condition and any intervention capable of affecting circulation.

Matched records for a before-and-after heat-run comparison
Comparison itemWhat should be matched or explainedEvidence of a meaningful difference
Applied heatingLosses, current, voltage, tap and load partitionDifferent heat-source distribution despite a similar total
Cooling systemPumps, fans, valves, circuit arrangement and actual operationChanged flow split or cooling capacity
Internal assemblyDuct geometry, insulation position, clamp condition and lead routesAn altered thermal or hydraulic path
Temperature measurementsProbe identities, positions, calibration and reference-time treatmentRelocation or acquisition changes that alter the measured quantity
Test environmentAmbient reference, enclosure and surrounding airflowA placement or recirculation effect unique to one run

Look for a spatial change before averaging it away

Compare the individual temperature traces as well as the final rise values. A change concentrated in one winding region is more suggestive of a local path or placement change than a uniform shift across every channel. The pattern is evidence for an investigation, not proof of its cause.

Check whether oil inlet and outlet behavior changed at the same time. A local hotter region with similar overall cooler performance may indicate redistribution rather than insufficient total cooling capacity. A changed total-loss input requires a different comparison.

Compare the two defined duties under the governing temperature-rise method [2]. Maintenance records [1] establish the actual cooling arrangement and interventions; they do not turn a different assembly or sensor position into a repeated identical test.

Compare a local change with a common shift

Assume matched before/after channels change by 1 K at three locations and by 8 K at one winding region. Relative to that common 1 K shift, the local excess is 7 K. Investigate channel position, duct geometry and flow at that region before averaging it into general test scatter. These are comparison assumptions, not a statistical acceptance rule.

Estimate scatter from observations that actually repeat the process

Instrument repeatability measured on a stable reference does not represent the variability of dismantling and rebuilding a transformer. Repeated unchanged runs characterize one part of the test variation. Controlled reassemblies, where available, provide evidence about a different part.

References

  1. U.S. Bureau of Reclamation, FIST Volume 3-30, Transformer Maintenance, 2000.
  2. IEC, IEC 60076-2:2011, Power transformers — Part 2: Temperature rise for liquid-immersed transformers.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing