Compare local and resistance-derived temperatures by their spatial and time definitions. A sensor at 120 °C and a resistance result of 100 °C can describe the same winding when a local hotter section sits above the conductor-path average. [1]
The first investigation is therefore a comparison of measurement definitions and times. Treating the readings as competing measurements of one identical temperature can send the investigation towards a calibration fault that does not exist.

Understand the averaging implicit in resistance
For one conductor material with an approximately linear resistance-temperature relation, the total resistance is the sum of its local contributions. The resulting converted temperature is weighted by each section’s reference resistance. For uniform material and cross-section this becomes a length-weighted conductor average under the stated assumptions.
In an illustrative two-section winding, suppose the sections have equal reference resistance and temperatures of80°C and120°C. The resistance-derived temperature is100°C, while a correctly positioned local sensor can read120°C. The20K difference describes the chosen thermal distribution; it is not evidence that either instrument is wrong.
| Observation | Possible physical explanation | Comparison needed |
|---|---|---|
| Local reading exceeds the resistance temperature | Sensor samples a hotter conductor region than the resistance-weighted mean | Sensor placement and the predicted spatial temperature distribution |
| Selected local reading is lower than the resistance temperature | The probe may sample a cooler region, another material or a poorly coupled position | Installation details and other temperature channels |
| Difference changes with cooling configuration | Oil-flow redistribution can change the local-to-average relation | Matched load, cooling state and actual channel locations |
| Difference appears only after shutdown | Sensor and resistance estimate may refer to different times or recovery models | Aligned acquisition times and resistance extrapolation record |
Check sensor position against the possible hot-spot locations
A fixed sensor measures its installation point. The hottest conductor location can differ from the predicted location or move when load partition, tap position or cooling changes. A low reading at one installed probe does not establish that the entire winding maximum is low.
Review sensor attachment, depth, thermal contact and channel identity. A probe installed in insulation or adjacent oil may measure a different thermal response from the conductor itself. These installation effects should be distinguished from a real conductor gradient.
A spatial thermal field can contain a local maximum above its weighted mean [2]. A stable difference between a probe and resistance temperature is therefore not a calibration correction until location, weighting and time have been reconciled.
Keep the resistance-weighted mean distinct
For the assumed two equal-reference-resistance sections at 80 and 120 °C, the converted mean is 100 °C and the local-to-average difference is 20 K. If the hotter section instead carries an assumed 75% reference-resistance weight, the mean becomes 110 °C. Use the actual conductor weighting and local probe position before calling their difference instrument error.
Resolve timing before applying an error allowance
A local sensor can provide a reading while heating is still applied. Resistance temperature may be reconstructed after shutdown. Compare the quantities at a consistent reference time and retain the extrapolation model and its sensitivity. Otherwise the subtraction includes both spatial and temporal differences.
References
- U.S. Bureau of Reclamation, FIST Volume 3-31, Transformer Diagnostics, June 2003.
- U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.