A GIC measurement chain must separate quasi-DC current from AC leakage, clipping, rectification and sampling error. Test the sensor, acquisition and saved record together with challenges that reproduce the relevant current range.
Bailey and colleagues describe a Hall-effect neutral-current channel with low-pass filtering and an early measurement range that clipped events [1]. Those are distinct limits: DC sensitivity does not establish adequate range or AC rejection for the installed chain.

Check what each stage can represent
A conventional current transformer relies on changing flux and is not a steady-DC sensor. A sensor specified for DC still needs an appropriate range, zero stability, bandwidth and isolation arrangement for the application. Its installation must follow the relevant equipment and safety requirements.
Document the analog sensor output, conditioning, analog anti-alias filter, sampling rate and any digital processing. A digital low-pass filter cannot undo aliasing that occurred during sampling. It also cannot reconstruct peaks removed by sensor or amplifier saturation.
Challenge the chain with known inputs
| Controlled input | Observation to retain | Failure it can expose |
|---|---|---|
| Verified zero current | Offset and its change with time and environment | Zero drift mistaken for GIC |
| Positive and negative DC levels | Gain, polarity and settling | Asymmetry, incorrect sign or poor DC response |
| AC with zero intended mean | Raw signal and reported quasi-DC output | AC leakage, rectification or sampling artifacts |
| DC superimposed on AC | Recovered DC versus the known applied value | Range loss and cross-sensitivity under realistic coexistence |
| Slowly changing DC | Amplitude and timing response | Excessive attenuation or delay in the desired band |
Use approved test equipment and an arrangement appropriate to the sensor; this table defines evidence requirements, not a field wiring procedure. Choose levels and frequencies from the anticipated service environment and the instrument’s permitted range.
For each challenge, retain the raw and processed records. State the expected result, measured deviation and uncertainty. Passing an isolated DC-gain check does not demonstrate AC rejection when the same chain encounters a large AC component.
Expose measurement-range failures
If a channel clips, mark the affected interval and the known range limit. A smoothed value below that limit can still have been calculated from clipped raw samples. The exact original peak is then unavailable without independent information.
Match the desired quasi-DC band to the event timescale. A very slow filter can conceal changes important to the magnetic input; a wide band can retain unwanted power-frequency content. Record the filter’s response and delay so later event comparisons use the actual measurement timing.
Calculate the AC leakage of an assumed measurement filter
Assumptions: a first-order low-pass filter with time constant 1.0 s, 1.0 A RMS at 50 Hz superimposed on 0.20 A DC, and no clipping or rectification. Its 50 Hz amplitude ratio is 1/√[1 + (2π50 × 1)²] = 0.003183. Residual AC is 3.18 mA RMS, 1.59% of the DC level. That ripple is not itself a DC bias, but an AC-only chain test must also check nonlinear rectification and sampling. Compare the recovered DC and remaining error with the stated uncertainty requirement [2]; digital filtering cannot repair earlier clipping.
Accept the chain against its stated measurement requirement and uncertainty budget. Resolve false quasi-DC output from an AC-only challenge before using the field record as a transformer-model input.