An open-phase event with connected motors evolves with machine flux, speed, load torque and control transitions. Compare that dynamic case with the no-load transformer model using the same conductor opening and source network, then follow the voltage and current histories through the event. [1] [2]

Keep the same physical opening
Specify the opened conductor, remaining source phases, transformer connection and observation points. Change the load representation while preserving that event definition. A complete source disconnection is not the same event as losing one conductor while other supply paths remain connected. [1]
For no load, retain magnetizing branches, relevant capacitance and instrument loading. For the motor case, add actual machine connections and parameters with the source and transformer impedances. A fixed load impedance cannot represent changing rotor speed or stored electromagnetic state.
| State retained | No-load study | Motor-dominated study |
|---|---|---|
| Transformer excitation | Magnetizing coupling and external paths | The same features plus changed load current |
| Machine electromagnetic state | Absent | Initial flux/current and appropriate dynamic equations |
| Mechanical state | Absent | Speed, inertia and torque-versus-speed behaviour |
| Connected-device state | Instrument and source topology | Also contactors, drives and permitted control transitions |
Separate voltage contribution from restoration
The motor-bus transfer paper describes voltage persisting after full source disconnection because machine electromagnetic state decays over time [3]. Use that evidence to retain the machine states. Its disconnected-bus decay is not the solution for an open-phase circuit still energized through remaining conductors.
Track phase-voltage angles, currents and directional power alongside voltage magnitude. A temporarily substantial motor contribution can mask one observation of the opening while producing another abnormal current or sequence pattern. It does not restore conductor continuity.
Follow speed and load together
Represent electromagnetic torque, load torque, losses and speed together. Liao and colleagues’ coupled sequence/network model retains negative-sequence effects during unbalanced voltage disturbance [2]. Define slip against the relevant rotating field and keep the initial electromagnetic state; a balanced steady-state motor impedance does not capture that evolution.
Include differing machine groups where an aggregate would hide relevant inertia, load torque or disconnection behaviour. Validate the aggregate for the event quantities being interpreted. One fitted bus-voltage trace cannot identify all omitted internal states.
Compare the complete timelines
Keep the same opened topology, source and initial conditions in the no-load and dynamic motor cases [1] [2]. Save the voltage/current histories and every contactor or control transition, then compare when the proposed detector’s observation becomes available.
Align the no-load and motor cases by opening time, initial machine state and source topology. Compare each detector’s observations through the complete timelines, and identify which motor parameters or switching transitions account for the differences in its coverage.
References
- J. LaBlanc, Y. Shah and J. Aultman, Schweitzer Engineering Laboratories, Revisiting Open-Phase Detection for Fuse-Protected Power Transformers, 2024.
- W.-P. Liao, Y. Zhang and R. Zhou, Analytical method to calculate transient responses of induction motor load, IET Generation, Transmission & Distribution, 2020. DOI: 10.1049/iet-gtd.2018.6107.
- P. Muralimanohar and coauthors, Implementation of a Microprocessor-Based Motor Bus Transfer Scheme, IEEE PCIC, 2016. DOI: 10.1109/PCICON.2016.7589248.