Include unequal ground and inter-conductor capacitances when interpreting voltage on an opened phase. Their physical locations, source potentials and measurement loading determine the coupled response. Use a linear model to screen that response, then test whether nonlinear magnetization or dynamic behavior requires a fuller assessment. [1] [2]

Keep all paths on the same drawing
Identify the actual transformer winding connections, opened element and remaining sources. Add cable, winding, instrument and other relevant capacitances at their physical nodes. Do not combine unlike locations into one number if the intervening impedances affect the response. [2]
Include the instrument input and its reference. A high-impedance voltage observation can differ from a more heavily loaded point because the measurement itself changes the node admittance. Comparing the two without their loading can falsely assign the difference to a defective sensor.
| Model element | Variation to represent | Output retained |
|---|---|---|
| Phase-to-ground capacitances | Actual phase asymmetry and uncertainty | Phase/reference voltage and displacement current |
| Interphase coupling | Connected conductor lengths and geometry | Potential supported from neighbouring phases |
| Measurement input | Burden, capacitance and reference path | Loaded versus intended observation |
| Conductive source/load paths | Confirmed topology and impedance | Distinction between coupling and delivered power |
Use admittance and complex voltage
In a linear sinusoidal screen, a capacitor contributes admittance jωC. Apply nodal KCL at the represented frequency and reference, including instrument loading. An open conductive path does not impose zero voltage at its remaining capacitively connected node.
For a simple floating node coupled capacitively to known potentials Ek, the ideal zero-leakage relation is Vn = Σ(CkEk)/ΣCk. This reduced formula assumes every included capacitance ends at a prescribed potential and no omitted conductive load or source impedance changes those potentials. It is not the equivalent circuit of every open-phase transformer.
Sweep asymmetry without changing the event
Vary evidence-based capacitance combinations while retaining the same physical opening. Inspect which measured phase potential, current or detector observation changes materially. Uniformly scaling all capacitances in the reduced ideal formula leaves its weighted voltage unchanged but changes displacement-current magnitudes; the full loaded circuit can behave differently. [1]
Ferracci’s technical report identifies capacitance, nonlinear inductance, circuit topology and initial conditions as controlling ferroresonance factors [2]. Use those features to flag cases beyond this linear screen. A large calculated voltage alone does not identify a resonance mechanism.
Deliver the source topology, capacitance ranges and instrument loading with the voltage and current sensitivities they produce. Identify the parameter region supported by the linear screen and the cases requiring a nonlinear dynamic model, so the coupled-voltage interpretation remains tied to the represented circuit.
References
- D. De Ronde, R. VanHatten and A. Wade, Schweitzer Engineering Laboratories, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, 2015.
- P. Ferracci, Schneider Electric, Ferroresonance, Cahier Technique No. 190, March 1998.