ARTICLETechnical article

Transformer Open-Phase Heating: Map Sequence Currents to the Windings

  • Chenfan Power

Map the measured sequence currents into the physical transformer windings before calculating open-phase heating. Winding connection determines conductor currents and circulating paths; the resulting local losses and thermal response establish the duty the transformer experienced. [1] [2]

Transformer Open-Phase Heating: Map Sequence Currents to the Windings: technical review table
Use a bounded resistance example

Recover the current in each winding

Identify the side on which currents are measured, phase order and sequence convention. Convert terminal currents to the actual winding currents using the connection and turns relationships. Delta line current and delta branch current are different quantities; an externally absent zero-sequence line current does not exclude a circulating winding current. [1]

Retain tap, load and source conditions. A single ratio of negative- to positive-sequence current cannot reconstruct an omitted circulating path or locate the highest conductor current.

Use a bounded resistance example

For three identical star-winding phase resistances R at one fixed temperature, symmetrical-component algebra gives Σ|Ip|² = 3(|I0|² + |I1|² + |I2|²). Their resistance-only loss is 3R times that sum. The identity assumes this physical phase-current set and equal resistance; it is not a complete stray-loss model.

Assume the resistance applies at a fixed 75 °C. Take assumed values R = 0.10 Ω, I1 = 100 A, I2 = 20 A and I0 = 0. Align the positive- and negative-sequence A-phase phasors. Phase magnitudes become 120 A, about 91.65 A and about 91.65 A.

Loss observationBalanced 100 A exampleSpecified unbalanced example
A-phase I²R1,000 W1,440 W
Each other phase I²R1,000 W840 W
Three-phase total3,000 W3,120 W

The total rises only 4%, while one phase’s resistance loss rises 44%. Neither percentage predicts temperature. Different sequence angles redistribute the phase currents, so the magnitude pair alone does not select the same limiting phase. [2]

Add the losses the identity omits

Evaluate relevant conductor eddy, structural and circulating-current losses using the actual field and frequency content. Resistance changes with temperature, and unequal windings require their own calculation. Keep the electrical loss boundary explicit rather than calling the simple identity total transformer heating.

Transfer spatial losses to the appropriate thermal model. Initial temperature, cooling state and event duration determine the excursion; a brief event and sustained abnormal duty require different histories. A measured average winding temperature may not identify the most heavily loaded local region.

Assemble the physical winding currents, local loss distribution, cooling state and event duration into the thermal assessment. Identify the loss mechanisms still outside the model and obtain the corresponding winding or structure data before judging the transformer’s open-phase duty.

References

  1. B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
  2. U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.