A common third-harmonic component cancels when phase potentials are subtracted to form a line voltage. At a floating transformer star point, phase-to-reference measurements can therefore expose a component that line-voltage measurements miss. Trace the reference and return paths to explain the difference.

Name the reference and the return paths
Identify the winding star point, any closed delta, grounding connection and phase-to-ground capacitances. Include the instrument input impedance and its reference connection. A meter can load a floating node, so a voltage prediction without the measurement circuit may describe a different condition. [1]
Keep magnetizing current paths distinct from terminal line-current observations. The SEL transformer-fundamentals discussion explains zero-sequence ampere-turn compensation and the significance of a closed delta or another magnetic return path [2]. It does not specify the third-harmonic amplitude of this transformer.
| Frequency-domain item | Path to draw | Observation |
|---|---|---|
| Fundamental excitation | Applied winding voltages and magnetizing network | Phase angles, magnitude and flux operating range |
| Third-harmonic current | Permitted internal/neutral return paths | Where the represented current can flow |
| Common third-harmonic voltage | Phase and star-point reference relationships | Phase-to-reference versus line subtraction |
| Measurement and capacitance | Actual input and displacement-current paths | Sensitivity to loading and reference choice |
Demonstrate common-component cancellation
Let each phase potential contain its own fundamental plus an identical third-harmonic waveform h(t). Direct subtraction va(t) − vb(t) removes h(t) exactly. Unequal harmonic amplitudes or angles leave a residual third harmonic in the line voltage.
Assume a phase waveform with a 230 V RMS fundamental and a 30 V RMS third harmonic. Its total RMS is √(230² + 30²) ≈ 231.95 V over complete periods. Orthogonality gives this relation. Peak voltage depends on relative harmonic phase; treating the result as a sinusoidal RMS does not determine it.
Separate distortion from resonance
Ferracci identifies capacitance, nonlinear inductance, circuit topology and initial conditions as controlling ferroresonance factors [3]. A distorted phase voltage alone does not establish resonance, its stability or its initiating event. Test that hypothesis against the corresponding circuit and dynamics.
Use synchronized phase-to-reference and line-voltage waveforms, with instrument bandwidth and reference recorded. Compare the predicted paths in an offline model over the relevant excitation and capacitance range. If an input is unsupported, show how that uncertainty affects the interpretation.
Compare synchronized phase-to-reference and line-voltage measurements against the modeled harmonic paths. Record the reference impedance, displacement-current route and excitation assumptions that explain the observed component; use those parameters to test the distortion and resonance hypotheses separately.
References
- D. De Ronde, R. VanHatten and A. Wade, Schweitzer Engineering Laboratories, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, 2015.
- B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
- P. Ferracci, Schneider Electric, Ferroresonance, Cahier Technique No. 190, March 1998.