Review a relocated internal connection through its complete physical envelope. The same electrical nodes can sit beside different grounded surfaces, windings and supports, changing clearances, field exposure, restraint and inspection access.

Describe the complete moved envelope
Overlay the original and proposed connection on the same assembled geometry. Include the joint body, insulation, fasteners, supports and the movement allowed by manufacturing tolerances. A centre-point displacement alone cannot describe the closest live-to-ground interface.
Record the original evidence boundary. A dielectric calculation may have represented one nearby grounded wall; a thermal observation may have covered an accessible joint surface. Moving the component can change both what it experiences and what an earlier observation actually supports.
| Changed surroundings | Physical comparison | Evidence dependency |
|---|---|---|
| Grounded metal and adjacent live parts | Clearance, barriers, edges and actual potentials | Local electric-field and dielectric assessment |
| Winding leakage field | Joint orientation and conductive parts within the field | Additional heating and force representation |
| Mechanical support | Span, contact and permitted displacement | Restraint under represented mechanical duty |
| Oil path and inspection access | Local flow obstruction and reachable observations | Thermal evidence and maintainable inspection coverage |
Use simple geometry only as a screen
All numerical inputs in this comparison are assumptions. For an illustrative uniform-field gap at the same voltage, reducing distance from 20 to 16 mm raises V/d by 20/16 = 1.25. This does not predict the peak field around a real joint. Edges, solid/liquid interfaces, voltage distribution and barriers can govern the local response. The calculation merely exposes why unchanged voltage does not imply unchanged stress.
Similarly, preserving current and conductor section does not preserve the leakage field around a joint. Compare the field-producing winding geometry and the connection’s new position. Where forces matter, include actual restraint and contact rather than calculating a free conductor force and assuming the support can carry it.
Check what the earlier test could see
If an earlier thermal test used a sensor at the old joint location, decide how the proposed location will be observed or otherwise represented. A satisfactory winding-average temperature cannot locate a new joint hotspot. Where relocation changes access, record any revised inspection method and its detection limit.
Put voltage on the clearance screen
Assumptions: a 100 kV instantaneous potential difference across a uniform gap. At 20 mm, V/d = 5.00 kV/mm; at 16 mm, it is 6.25 kV/mm, a 25% rise. These are field estimates, not withstand limits. IEC 60243-1 covers power-frequency electric-strength tests of solid insulating materials [1], rather than this assembled joint. Assess its actual edges, barriers and duty; record the moved envelope and potentials in the revision [2].
Issue the revised assembled envelope with evidence for each changed electrical, thermal and mechanical interface. Retain continuity results for the current path they still represent, and assign the new clearance, support and observation questions their own verification.
References
- IEC, IEC 60243-1:2013, Electric strength of insulating materials — Test methods — Part 1: Tests at power frequencies.
- NASA, NASA Systems Engineering Handbook, section 6.5, Configuration Management, official online text.