Trace a hot-resistance drift through the circuit between the voltage-sensing points. Cooling at an included terminal or series joint can change the measured voltage alongside winding cooling and bias the converted conductor temperature. [1]
Four-wire measurement separates current delivery from voltage sensing. Its benefit depends on where the sense connections actually sit. The measured resistance belongs to the circuit between those points, not automatically to the winding conductor alone.

Draw the sensing boundary before correcting anything
Mark the two current connections and the two voltage-sensing points on the terminal arrangement. Identify which bushings, leads, joints, tap contacts or external links lie within the sensed path. Some of these belong in the required terminal-to-terminal resistance test. Their inclusion still matters when that resistance is converted into a conductor temperature.
| Contribution | Four-wire implication | Useful comparison |
|---|---|---|
| Current-lead drop outside the sense points | Excluded by a correctly connected Kelvin arrangement | Verify the sense points and current path on the actual setup |
| Series joint inside the sensed path | Included in the terminal-to-terminal reading | Track joint temperature and the defined circuit configuration |
| Thermoelectric voltage at dissimilar heated connections | Can add to the sensed voltage independently of winding resistance | Use an instrument-supported offset check with thermal stability established |
| Changing test current or unsettled inductive response | Can disturb the inferred resistance | Review current and voltage traces before accepting the point |
Do not relocate sense connections midway through a qualification sequence without recording and evaluating the change. A new sensing boundary can produce a step that resembles sudden cooling but measures a different circuit.
Estimate whether the connection effect is consequential
Suppose, illustratively, the cold reference resistance is 0.100 Ω at 20 °C and the handbook copper constant is 234.5 °C [1]. A changing included series contribution of 0.00020 Ω changes the converted temperature by (234.5 + 20) × 0.00020/0.100 = 0.509 °C. The direction follows the resistance drift: a decreasing contribution lowers the reported temperature.
The example treats the cold reference as fixed. If connection contributions change in both hot and cold readings, examine the ratio rather than subtracting only the hot contribution. Different conductor materials and temperature distributions also limit the interpretation of the complete circuit as one uniform winding temperature.
For a corrected resistance ratio, propagate hot and cold input uncertainties with covariance where they share connection or calibration effects [2]. Repeated stable readings alone cannot identify an included joint contribution or establish that the measured path equals the intended winding boundary.
Quantify the included-series contribution
With handbook copper constant 234.5 °C [1], assumed 20 °C cold reference and 0.100 Ω cold resistance, a 0.00020 Ω included-series drift changes converted temperature by 0.509 K. Identify that contribution’s boundary and temperature before any correction. Kelvin leads exclude drops outside the sensing points; an included joint remains part of the measured path.
Use a connection comparison that preserves the measurand
Record terminal temperatures, sense-point photographs and the electrical boundary for both cold and hot measurements. Compare repeat measurements under controlled connection conditions when permitted by the test method. A stable reference circuit can help identify instrument or external connection drift without assuming that the winding itself is stable.
References
- U.S. Bureau of Reclamation, FIST Volume 3-31, Transformer Diagnostics, June 2003.
- B. N. Taylor and C. E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994, sections 5 and 6.