Trace each heat-run column to the physical probe and installed location. A channel swap can assign a plausible curve to the wrong position. Verify identity through wiring, acquisition and export as part of the controlled configuration [1].
The required chain is short and specific: physical probe identity, installed position, acquisition input and exported data column. Every change during the run must preserve that chain.

Connect the physical installation to the recorded channel
Use a drawing or installation photograph that identifies the probe position unambiguously. A label such as “upper winding” may be insufficient when several windings, phases or heights have sensors. Record the probe identifier and input separately; channel numbers should not be treated as permanent sensor identities.
| Interval | Probe | Installed location | Acquisition input | Exported column |
|---|---|---|---|---|
| Start to recorded replacement event | P17 | Winding1, phaseB, positionB3 | Input08 | T_W1_B_B3 |
| After replacement event | P44 | Same verified positionB3 | Input08 | T_W1_B_B3, replacement marker retained |
| Entire run | P18 | Winding1, phaseB, positionB4 | Input09 | T_W1_B_B4 |
These identifiers illustrate a record format, not an actual test. Reusing input08 does not make the replacement probe identical: calibration correction and uncertainty can differ [2], as can installation and response. Retain the replacement event and verify its new physical-to-export mapping.
Verify the mapping before heating and after interventions
Use the identification check supported by the sensing and acquisition equipment to confirm the recorded mapping before the run. Keep its outcome with the installation record. A display label copied from a previous test is not independent evidence of the present wiring or optical connection.
After a probe or input change, verify both the physical connection and the exported column assignment. Record whether the installation position changed, whether a correction was updated and when the revised mapping became valid.
Preserve physical item identity, the applicable configuration baseline and every documented change so the record describes the same object that was measured or examined. [1]
Test identity using an independent channel change
Assume the installation check gives probe P17 a documented 5 K controlled response while neighboring P18 remains unchanged. If the exported P18 column shows that response instead, the mapping is contradicted. Preserve both raw columns and resolve the physical-to-export association before using either curve as a winding-location result.
Use thermal patterns to investigate mapping errors
An unusual response can reveal a swapped channel, but similar neighboring responses cannot prove that labels are correct. Cross-check the physical mapping when an unexplained temperature ordering appears. Do not relabel curves solely to make them agree with a predicted temperature distribution.
References
- NASA, NASA Systems Engineering Handbook, section 6.5, Configuration Management, official online text.
- B. N. Taylor and C. E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994, sections 5 and 6.

