Dry-Type Transformer Temperature Sensors: Contact and Reading Bias

  • Chenfan Power

Qualify the installed temperature sensor through its thermal contact and competing heat paths. Weak contact with the target surface gives mounting, leads and surrounding air more influence on the reading and response time. [1]

This issue concerns the sensor installation. It should be investigated separately from the transformer’s insulation temperature class or the conversion from winding resistance to average temperature.

Dry-Type Transformer Temperature Sensors: Contact and Reading Bias: technical review table
A second thermal path can pull the reading away

Identify the surface the sensor is meant to represent

Record whether the sensing element contacts conductor insulation, cast resin, a defined pocket or nearby air. Those are different local thermal quantities. A temperature specified for the conductor cannot be equated automatically with a reading taken from an accessible resin surface.

Check insertion depth, contact area, gap, retaining pressure and any specified interface material. Installation changes can affect both the steady reading and response time. Use the sensor and equipment manufacturer’s permitted arrangement rather than introducing an unqualified filler or adhesive.

A second thermal path can pull the reading away

For an illustrative steady sensor with negligible self-heating, consider contact conductance Gc to a surface at Ts and lead or mounting conductance Gl to a region at Tl. Ignoring other paths for this example, Tsensor = (GcTs + GlTl)/(Gc + Gl).

Illustrative contact effect with the other inputs fixed
Installation caseSurface / lead-region temperaturesContact / lead conductancesSensor temperature
Higher contact conductance100 /30°C0.050 /0.005W/K93.6 °C
Lower contact conductance100 /30°C0.010 /0.005W/K76.7 °C

The selected numbers are an illustration, not sensor specifications. Reducing contact lets the cooler lead-region path exert more influence. If that region were hotter than the target surface, the direction of the bias could reverse. A real installation can also involve convection, radiation and sensor self-heating.

A repeatability-only budget does not establish surface temperature when contact conductance or the lead-region path is uncertain. Include relevant systematic contributions and covariance in the measurement model [2]; repeated stable readings can retain the same installation bias.

Use the conductance comparison as an installation decision

For the stated assumed 100/30 °C boundaries, the conductance model gives 93.64 °C with 0.050 W/K surface contact and 76.67 °C with 0.010 W/K contact, keeping the 0.005 W/K lead path fixed. The 16.97 K difference justifies checking installation and response before attributing the changed reading to the winding.

Compare installations without changing the target quantity

Use a controlled, representative temperature comparison where the approved setup permits it. Keep location and reference conditions fixed while investigating contact or routing. A second sensor at a different depth may read differently because it samples another gradient, even if both installations are sound.

References

  1. U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.
  2. B. N. Taylor and C. E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994, sections 5 and 6.