Place the operated fuse on the transformer bank’s full connection drawing, then redraw the circuit that remains energized. A primary conductor, secondary branch and instrument-circuit opening produce different networks; each single-phase unit’s polarity and winding connection determine the surviving paths. [1]

Place the fuse on the full connection drawing
Name each single-phase unit, winding polarity and external terminal. Include the source conductors, bank interconnections and load return paths. Record whether the operated fuse lies outside a winding loop or removes one of its branches. [2]
Do not infer the bank from the sum of its nameplate capacities. A common three-limb transformer and three independent magnetic units can share a nominal vector-group description yet differ in magnetizing coupling. Keep the actual construction in the model.
| Opening location | Equivalent-circuit change | Remaining-path question |
|---|---|---|
| Primary supply line | One external source connection removed | Which winding loops remain fed by the other source lines? |
| Individual bank winding branch | The affected internal branch removed | How does the bank connection redistribute load and voltage? |
| Secondary feeder conductor | The downstream load connection removed | Which loads or other sources can still energize the region? |
| Instrument fuse | Measurement path impaired | Which indicated voltages changed without a primary opening? |
Trace the surviving supply and fault paths
For the represented primary opening, follow the remaining source voltages through the actual winding connections. Identify series-associated branches, closed loops and coupling to the loads. Compute current and voltage together; nonzero voltage does not establish the original load-supply capability. [1]
Include the fault that initiated the fuse operation if it remains present. A cleared upstream contribution does not prove that every downstream fault-current path disappeared. The SEL Dyn study shows why fuse location, connected load and a permanent fault must be assessed together in its specified application. [2]
Separate load connections
Compare the actual single-phase line-to-neutral, line-to-line and three-phase loads. Their post-opening paths differ. Passive impedances, rotating machines and controlled electronic loads can respond differently, so one constant-impedance result cannot stand for the entire feeder. [2]
Retain other sources and their operating states. If a motor or inverter contributes voltage, identify that contribution and its duration. Do not label a bank fully restored merely because a downstream voltage subsequently resembles its earlier magnitude.
Keep the result tied to the bank
Save the intact and opened equivalent circuits with matched phase identities and measurement points. List winding currents, branch voltages, unresolved source/load dynamics and protection observations for that topology. [2]
Compare the intact and opened bank models using branch currents, load voltages and surviving fault paths. Keep an accidental fuse-open state distinct from a designed open-delta bank, and identify the source, load and protection information needed to explain the event.
References
- B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
- J. LaBlanc, Y. Shah and J. Aultman, Schweitzer Engineering Laboratories, Revisiting Open-Phase Detection for Fuse-Protected Power Transformers, 2024.