Mapping Unequal Phase DC Currents in a Transformer Bank

  • Chenfan Power

Each unit in a bank of single-phase transformers has its own DC current path and thermal history. Allocate the signed neutral-current sum to those paths, then assess the local exposure of each transformer. [1]

Regional GIC models need explicit transformer and grounding connections. The subsequent equipment assessment must retain the current allocation relevant to each magnetic circuit, rather than replacing it with a convenient bank average. [2]

Mapping Unequal Phase DC Currents in a Transformer Bank: technical review table
Build a phase-specific exposure map

Declare the sign and path of each current

For a common neutral with a consistent orientation, IN = IA + IB + IC. This is a signed summation, not a rule that each current equals IN/3. If several neutrals or common winding sections exist, use their actual nodes and section currents.

For an illustrative bank of equal-turn single-phase units, IA = 8 A, IB = 3 A and IC = 1 A produce IN = 12 A. Assigning 4 A to every phase would understate phase A’s current by half and overstate phase C’s by a factor of four. These assumed numbers demonstrate allocation error only.

Build a phase-specific exposure map

Phase recordRequired inputResult to retain
Electrical pathLine, winding and grounding connectionsSigned DC current for the relevant section
Magnetic excitationTurns and winding orientationSigned sum of turn-current products
AC operating conditionVoltage, load and waveformComparable baseline for that phase
Local thermal responseConstruction, initial temperature and durationPhase-specific governing location and history
Measurement supportIndependent channels and uncertaintyWhether the allocation is measured or inferred

Equal current does not guarantee equal ampere-turns when winding sections or turns differ. For autotransformer arrangements, a high-voltage terminal current and a common-section current can contribute differently to the signed magnetic input. Preserve those contributions before comparing phases.

Check why the distribution became unequal

Inspect the represented branch DC resistances, parallel circuits and available grounding paths. A changed phase configuration can be a topology issue rather than a resistance tolerance. Verify that the network model did not force equality through a merged node that removes the physical distinction.

One neutral monitor cannot uniquely recover three unknown phase currents. Additional measurements or a supported network calculation are needed. If the allocation remains uncertain, assess credible phase distributions consistent with the observed sum instead of presenting the equal division as measured fact.

A single-phase bank and a three-phase unit also have different magnetic coupling. Do not transfer a bank’s independent-unit response directly into a common-core model without representing the shared flux paths.

Carry the phase allocation into local-loss and thermal calculations and identify the governing unit. Preserve its current and cooling history throughout the assessment.

References

  1. NERC, Transformer Thermal Impact Assessment White Paper, Project 2013-03 Geomagnetic Disturbance Mitigation, October 2017.
  2. R. L. Bailey and coauthors, Modelling geomagnetically induced currents in midlatitude Central Europe using a thin-sheet approach, Annales Geophysicae 35, 2017. DOI: 10.5194/angeo-35-751-2017.