Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Open-Neutral Electronic Loads: Include Regulation and Dropout States

  • Chenfan Power

Model electronic-load current from its actual regulation and dropout states when calculating an open-neutral star point. The SEL analysis distinguishes constant-power and constant-current loads from fixed impedances [1]. The following branch-law comparison shows why that distinction matters.

Open-Neutral Electronic Loads: Include Regulation and Dropout States: technical review table
Compare the branch laws explicitly

State what the power stage actually controls

Identify the input circuit, regulation objective, stored energy and protection states. A passive rectifier, controlled input and drive with changing mechanical load require their own supported current laws; matching rated watts does not establish identical behaviour.

Retain whether the chosen quantity is AC input power, DC output power or a commanded load. Losses and power factor belong in a real input model. A constant-power approximation is bounded by the voltage, current and control conditions over which regulation is supported.

Compare the branch laws explicitly

Assume a unity-power-factor 1,000 W RMS branch at 230 V. Using P = V²/R gives 52.9 Ω at that point [2]. The following rows compare separate assumed branch laws at 180 V; they are not measured electronic-device responses.

Assumed branch model at 180 VCurrentInput powerLimit of interpretation
Fixed 52.9 Ω resistance3.40 AAbout 612.48 WPassive linear model
Ideal regulated 1,000 W5.56 A1,000 WValid only while the modeled regulator can sustain it
Current-limited deviceFrom its supported limit/modelFrom actual voltage and currentCannot retain unlimited constant power
Disconnected deviceRepresented leakage or remaining input pathCorresponding residual inputOutput-off does not necessarily mean every input path is open

Solve star-point balance with the changing laws

Replace a fixed admittance with the appropriate branch-current relation, including phase and waveform where relevant. Enforce node balance with the actual neutral and other returns. A constant-admittance star formula cannot retain a pre-event nominal resistance after the chosen load law changes.

For a constant-power approximation, increasing current as voltage falls can materially change the solution. Verify convergence and whether the solution remains inside the regulator’s valid range. A mathematical equilibrium beyond a current limit is not a physically supported operating point.

Retain transitions and stored energy

Include the relevant undervoltage exit, delay, reset and restart state from actual device evidence. Stored energy can separate the input-current transition from the downstream load response. The SEL analysis explicitly distinguishes constant-power and constant-current loads from fixed impedances [1]; use that distinction without assigning a generic dropout threshold to a real device.

Compare the resistor and controlled-load solutions using the device’s regulation range, current limit, dropout and restart data. Mark where their star-point voltages or operating states diverge, and obtain the missing transition data before extending the model through those states.

References

  1. J. LaBlanc, Y. Shah and J. Aultman, Schweitzer Engineering Laboratories, Revisiting Open-Phase Detection for Fuse-Protected Power Transformers, 2024.
  2. U.S. Department of Energy, DOE-HDBK-1011/3-92, Electrical Science, Volume 3, June 1992.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing