Radial Winding Buckling: Separate the Free Mode from the Support-Controlled Mode

  • Chenfan Power

Assess radial winding stability in two mechanisms: global circumferential distortion and deformation controlled by the support layout. Apply the boundary conditions, contacts and stiffness representation appropriate to each, then compare their controlling failure quantities.

Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.

Use the free-mode model to test the winding’s overall circumferential stability. Use the support-controlled model to test the spans, contacts and imperfections created by the actual support arrangement.

State what “free” and “forced” mean in the model

In the comparison here, the free radial mode can develop a global circumferential shape without discrete radial supports fixing its nodes. A support-controlled, or forced, mode is constrained by the circumferential support locations and can bow between them.

The free case still has its declared winding connections, layer interactions and material constraints. “Free” does not mean removing every mechanical restraint. The forced case also needs a contact model: a support that can separate, compress or slip is different from a permanently fixed node.

Identify whether the inward radial load is carried by individual conductors, a bonded pack or a layered assembly with relative motion. The bending stiffness and admissible modes depend on that representation.

Use the circumferential shape to identify the mechanism

A global mode may involve a low circumferential wave number, with several winding sectors moving together. A span-controlled mode has displacement features tied to support positions and unsupported arc lengths.

Plot radial displacement against circumferential position and overlay the actual supports. Check whether the computed nodes follow the support pattern or whether the winding and supports move together. A contour plot without those locations can hide the distinction.

For an instability calculation, inspect the preloaded or loaded equilibrium state before evaluating the tangent stiffness. If contact changes during loading, the admissible mode can also change. The lowest eigenmode from one fixed support state is not automatically the controlling mode of the evolving assembly.

A local support-span calculation

An original straight-beam surrogate isolates the effect of unsupported length. Let a conductor-like strip have E = 100 GPa, width b = 10 mm and radial bending thickness t = 3 mm. Its second moment is:

I = bt³/12 = 2.25e-11 m⁴.

For a pin-ended straight span under axial compression, the elastic Euler load is:

P_cr = π²EI/l².

At an assumed span l = 120 mm, P_cr = 1.542 kN. Halving the span to 60 mm gives 6.169 kN, four times larger.

The pin-ended relation follows from the elastic beam equation EI w″ + P w = 0 and its zero-deflection end conditions. An ideal midpoint brace admits half the original wavelength and raises this ideal load fourfold. Use the result to test support sensitivity before introducing winding curvature and contact.

Constructed straight-span caseUnsupported lengthElastic pin-ended critical load
Wider support spacing120 mm1.542 kN
Added ideal midpoint support60 mm6.169 kN

The same strip and elastic modulus give different limits because the support changes the mode. A real circumferential span also requires curvature, load distribution and actual contact stiffness.

Illustrative free global radial shape and between-support bows, with a separate straight-beam critical-load comparison at two support spans.
Global and support-controlled radial deformation shapes

Build the free-mode evidence set

Retain winding radius, conductor or pack bending properties, layer coupling, radial force distribution, initial ovality and the constraints that resist overall distortion. Include material nonlinearity when the computed stress approaches the applicable constitutive range.

Seed plausible global imperfections rather than relying on a perfectly circular geometry to create them numerically. Compare the mode and load path across reasonable imperfection amplitudes. Track whether a support ring or inner cylinder participates in the deformation.

A free-mode calculation should identify its circumferential shape, controlling stiffness and the effect of the retained global restraints. It should not inherit the short support-span formula as an overall winding limit.

Build the support-controlled evidence set

Use the actual circumferential positions, effective unsupported lengths, support widths, stiffnesses and attachment details. Include gaps, local conductor imperfections and any support that can lose contact.

Distinguish an ideal brace from a compressible support. A midpoint block improves the limit only to the extent that it develops the required reaction in the relevant direction. If the support compresses or detaches before the assumed mode load, the ideal fourfold beam result is not realized.

Evaluate local bending and contact stresses alongside the instability measure. A support can shorten a span while creating a new concentrated-load or insulation-compression limit at its edge.

Select the controlling mechanism

Run the two models with consistent material and load bases, then compare the admissible modes and failure quantities. If the global mode controls, improving one local span may have little benefit. If an unsupported sector controls, changing its support layout can be decisive.

Hand over the controlling mechanism, its loaded support state and the geometry or stiffness input that sets the margin. Tie the displacement shape and reaction path to the assembled construction so the next support or winding change targets that mechanism.

IEC 60076-5 addresses a transformer’s thermal and dynamic ability to withstand external short circuits. Keep that assembly-level assessment separate from the straight-span stability model developed here. [1]

NIST TN 1297 provides the measurement-uncertainty basis for retaining influence quantities and covariance. Apply that bookkeeping to the declared inputs and comparison metric rather than treating numerical agreement as a measurement uncertainty. [2]

References

[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.

[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.