Test which internal voltage states the measured terminals can distinguish. Use the input-output model to identify observable combinations and hidden directions before reporting a reconstructed winding waveform.
Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.
Perform that test before presenting an internal voltage waveform as evidence. A forward-model prediction and a state reconstructed from measurements are different results, even when they use the same circuit parameters.
Declare the states, inputs and outputs
For a linear state model, write dx/dt = Ax + Bu and y = Cx + Du. Define the internal voltage states, known applied inputs and measured outputs with their units and reference nodes.
For known input u, classical observability asks whether different initial states can produce the same complete output history. The observability matrix is:
O = [C; CA; CA²; …; CA^(n−1)].
Full column rank identifies all n state components in the exact declared model. A rank deficiency identifies hidden combinations. Scaling changes numerical conditioning, so use declared state and time normalization when comparing singular values or small rank margins.
The original multiport modal-fitting analysis shows that terminal responses and conditions expose different modes and error amplification. The state-observability test here goes further: it checks whether the chosen measurements distinguish the internal coordinates at all.
Construct a physical two-state counterexample
Use two parallel branches connected to the same input voltage u. Each branch contains a 10 kΩ resistor followed by a 100 nF capacitor to reference. Let x₁ and x₂ be the two capacitor voltages. Both time constants are 1 ms.
The state equations are:
dx₁/dt = 1,000(u − x₁)
dx₂/dt = 1,000(u − x₂).
Measure only the total terminal current:
I = (2u − x₁ − x₂)/R.
Since u is known, this measurement determines z = 2u − RI = x₁ + x₂. It does not directly measure either internal capacitor voltage.
Using normalized time τ = t/(1 ms), A becomes −I₂ and the output row is C = [1, 1]. The normalized observability matrix is [[1, 1], [−1, −1]], with rank one. The difference state x₁ − x₂ is hidden.
Identical terminals, different internal maxima
Set u = 0 and compare two initial states:
Case A: x(0) = [1, 0] V
Case B: x(0) = [0.5, 0.5] V.
Both produce z(t) = exp[−t/(1 ms)] V and I(t) = −100 µA × exp[−t/(1 ms)]. Every terminal-current sample is identical in the ideal model.
At t = 0, however, the maximum internal voltage is 1 V in Case A and 0.5 V in Case B. At t = 1 ms, those maxima are 0.367879 and 0.183940 V. A terminal fit cannot choose between these two internal distributions.
The example is an original RC network, not a claimed transformer measurement. Its role is to demonstrate an exact hidden state with physical energy-storage elements.

Add information that observes the hidden state
An additional ideal output z₂ = x₁ − x₂ supplies the missing direction. The two-output matrix [[1, 1], [1, −1]] has rank two and allows direct recovery:
x₁ = (z + z₂)/2, x₂ = (z − z₂)/2.
In a transformer study, that second output may require another accessible terminal response, a supported internal measurement or a different coupling that makes the hidden mode visible. A desired internal sensor cannot be treated as available merely because it appears in the simulation.
Changing the represented dynamics can also distinguish the states. If the two decay rates are 1,000 and 2,000 s⁻¹, the normalized observability matrix becomes [[1, 1], [−1, −2]], with nonzero determinant −1. The output contains two distinct exponential contributions.
Exact rank is not the practical accuracy test
With rates 1,000 and 1,010 s⁻¹, the same matrix is technically full rank, but the two responses are close over a short window. At 1 ms, initial states [1, 0] and [0, 1] produce outputs 0.367879 and 0.364219 V, a separation of only 3.660 mV.
Compare that separation and the complete-window sensitivity with supported measurement noise, timing error and model uncertainty. Extending the observation window or adding another output can improve separation; a nominal rank result alone does not establish reconstruction precision.
Check the observer or inverse calculation against independent data and physically admissible initial states. Report which internal quantities are and which remain sensitive to assumptions.
Separate inference from imposed initial conditions
If both capacitors are assumed initially uncharged and the input is known, the symmetric forward model predicts x₁ = x₂. That prediction is legitimate under its assumptions. It does not prove that the terminal-current measurement has observed the hidden difference state.
The same distinction applies to winding models initialized at a specified charge state. Retain the source of that initial condition and the uncertainty in internal parameters. An apparently precise reconstructed waveform may owe its precision to fixed assumptions rather than measurement information.
Release the observable combinations, hidden state space, measurement window and uncertainty with the reported voltage. For a hidden quantity, provide the prediction together with its imposed assumptions or obtain an additional discriminating measurement before claiming measurement-based verification.
Gustavsen and Heitz show that fitted multiport accuracy depends on terminal conditions and the visibility of small modes. Validate the response used for the engineering decision under its actual terminal loads. [1]
NIST TN 1297 provides the measurement-uncertainty basis for retaining influence quantities and covariance. Apply that bookkeeping to the declared inputs and comparison metric rather than treating numerical agreement as a measurement uncertainty. [2]
References
[1] B. Gustavsen and C. Heitz, Modal Vector Fitting: A Tool for Generating Rational Models of High Accuracy with Arbitrary Terminal Conditions, 2008, DOI:10.1109/TADVP.2008.927810.
[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.