Calculate outer-winding hoop stress from the load assigned to each conductor position, its local radius and load-bearing area. Retaining that force distribution exposes the maximum that a mean-radius estimate can conceal.
The design decision belongs to the maximum local stress under the declared load case. An average winding force or average radius answers a different question.
Derive the ring equilibrium first
For a thin circular conductor ring of radius r, let q be a uniform outward radial line load in N/m of circumference. A small arc dθ carries radial force q r dθ. The radial components of the two circumferential end forces give approximately N_θ dθ. Equilibrium therefore gives:
N_θ = q r,
and the membrane hoop stress is:
σ_θ = q r/A.
Here A is the conductor’s load-bearing cross-sectional area. The derivation assumes a thin ring with axisymmetric load and membrane action. It is not a thick-winding stress solution or a contact-load-sharing model.
Use the electromagnetic load in the units required by the mechanical representation. A volume force density must be integrated over the represented conductor section before becoming q. Multiplying an already integrated line load by the section again would count the area twice.
Preserve radial position in the load mapping
Each radial location can have a different electromagnetic field and force distribution. Map the calculated force to the conductor or layer that carries it. Keep the radius, section area, material state and connection to neighboring layers with that entry.
If layers share load through contact, bonded insulation or supports, represent that mechanism explicitly. Treating every conductor as an independent ring is useful for a transparent benchmark, but it cannot describe redistribution in a strongly coupled pack.
For nonuniform circumferential loading, include bending and support reactions. In a linear section calculation the combined stress contains membrane and bending terms, N/A ± Mc/I. Map each term to the same conductor section.
A radial-force distribution
Assumption: Consider independent thin rings with the same A = 100 mm². Let radius vary from 0.200 to 0.260 m and prescribe an outward line load that increases linearly from 10 to 30 kN/m:
q(r) = 10,000 + [20,000/0.060](r − 0.200) N/m.
The stress at each position follows from q(r)r/A.
| Radius | Outward line load | Membrane hoop stress |
|---|---|---|
| 0.200 m | 10 kN/m | 20.00 MPa |
| 0.215 m | 15 kN/m | 32.25 MPa |
| 0.230 m | 20 kN/m | 46.00 MPa |
| 0.245 m | 25 kN/m | 61.25 MPa |
| 0.260 m | 30 kN/m | 78.00 MPa |
Using the mean radius 0.230 m and mean load 20 kN/m gives 46 MPa. The maximum is 78 MPa, so the mean-input estimate is 41.026% below the maximum in this example.
Even the average stress is not exactly 46 MPa. With uniform averaging over radial position, the average of q(r)r/A is 47 MPa. The positive correlation between q and r adds a contribution that multiplying their separate means misses.

Identify what controls the peak
The constructed example has its maximum at the outermost ring because both radius and load increase outward. A real load distribution can peak elsewhere, and a smaller conductor area can create the controlling stress even where the force is lower.
Check the full radial and circumferential map. Include axial position if the electromagnetic force or structural constraint varies along the winding height. Report the peak’s location and the conductor geometry used to calculate it.
A continuum winding model may distribute stress through radial and shear interactions. Validate its load transfer and compare the local conductor quantity needed for the decision. A smooth averaged stress field can conceal a highly loaded individual conductor or support interface.
Keep strength and deformation on the same basis
Compare the controlling stress with the applicable material and assembly criterion at the stated temperature and loading history. Retain the actual conductor temper, area and constitutive model. The selected electromagnetic case and mechanical boundary conditions must belong to the same configuration.
If yielding, bending or contact redistribution is material, solve the nonlinear response instead of treating the membrane estimate as a complete instability or permanent-deformation limit. The ring calculation identifies a load-to-stress mechanism; the final acceptance uses the relevant conductor and assembly evidence.
Release a distribution-based conclusion
A useful handover includes the radial force map, integration basis, local radii and areas, load-sharing assumptions, and the maximum hoop or combined stress. State whether the reported value is a conductor stress, a layer average or a continuum field.
Report the controlling position and the input that makes it critical. In this constructed map, the outer conductor reaches 78 MPa while the mean-radius estimate gives 46 MPa. Carry the local load, radius and section into the material and assembly acceptance check.
David Roylance. Stresses in Beams. MIT, 2000, curvature, bending moment and normal-stress derivation.
IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]
Carry uncertainty in the measured model inputs and responses into the comparison, including correlated contributions. [2]
References
[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.
[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.