Helical Winding Telescoping: Track Relative Motion and the Actual Force Components

  • Chenfan Power

Track telescoping through adjacent-turn displacement and section rotation. Whole-winding axial translation leaves relative spacing unchanged; the local coordinates identify which support or insulation interface actually changes under load.

The force model must also retain the helical current direction and the local field components. Pitch does not convert every radial force into an axial force.

Resolve the helical conductor direction

For a helix of radius R and axial pitch p per revolution, define tan β = p/(2πR). Its unit tangent is:

t = cos β e_θ + sin β e_z.

For local magnetic field B = B_r e_r + B_z e_z, the conductor line force is q = I t × B. With the stated cylindrical orientation:

q_r = I B_z cos β

q_z = −I B_r cos β

q_θ = I B_r sin β.

The following components are the direct cross product of the stated local current direction and magnetic field. Keep both vectors in the same cylindrical coordinate system.

A purely axial field B_z gives a radial force in this model, not an axial component. The radial field B_r produces the axial force and a pitch-dependent circumferential component. This distinction prevents a geometric slope rule from assigning the wrong force direction.

A force-component calculation

Assumption: Choose R = 0.150 m, p = 20 mm, I = 1,000 A, B_r = 0.10 T and B_z = 0.20 T. The pitch angle is 1.216°.

The line-force components are approximately q_r = 199.955 N/m, q_z = -99.977 N/m and q_θ = 2.122 N/m. Their relation is q_θ/(−q_z) = tan β = 0.021221.

These values describe a chosen local field and current direction. Integrate the actual force distribution over each represented conductor region and retain its sign. A net axial force on the whole winding can be small while neighboring regions carry large opposing forces.

Separate translation, telescoping and tilting

Let u_j be the axial displacement of turn or layer j. A rigid axial translation has u_j = U for every j and leaves relative gaps unchanged. A telescopic measure is d_j = u_(j+1) − u_j; it records a change in local pitch or spacing.

A conductor cross-section rotation φ_j is a separate coordinate. It can change edge contact and support loading without producing the same displacement pattern as a rigid axial shift. Retain it where section tilting matters.

Plot absolute displacement, adjacent relative displacement and section rotation separately. The largest absolute u_j does not necessarily identify the controlling local distortion.

Helical radial, axial and circumferential force components, followed by translation, telescopic displacement and rotation coordinates and a restraint sensitivity ledger.
Helical force components and relative axial motion

A relative-restraint benchmark

Use a two-coordinate axial model with support stiffness k₀ from each coordinate to reference and interturn restraint k_t. Its elastic energy is:

W = ½k₀(u₁² + u₂²) + ½k_t(u₂ − u₁)².

For equal and opposite forces F₁ = +F and F₂ = −F, equilibrium gives u₁ = F/(k₀ + 2k_t) and u₂ = −u₁. Choose F = 100 N and k₀ = 20 kN/m.

Constructed loading/restraint caseu₁u₂Relative displacement u₂ − u₁
Opposing forces, k_t = 80 kN/m+0.556 mm−0.556 mm−1.111 mm
Opposing forces, k_t = 10 kN/m+2.500 mm−2.500 mm−5.000 mm
Both forces +100 N+5.000 mm+5.000 mm0

The last case is independent of k_t in this symmetric model because no relative displacement stretches the interturn restraint. It has larger absolute movement than the strongly restrained opposing-force case, yet no telescopic gap change.

All stiffnesses are positive, so this benchmark is stable linear deformation. It demonstrates relative-motion sensitivity; an instability calculation additionally needs load-dependent tangent stiffness, contact and geometry.

Identify the restraint that can change state

Retain turn-to-turn contacts, spacers, end constraints and any layer coupling that transfers axial load. If friction supplies restraint, identify the normal load and slip condition. If a bonded or wrapped interface supplies restraint, use evidence for that interface rather than an arbitrary fixed displacement.

Track when a contact opens, a support compresses or relative slip changes the load path. A stiffness valid before slip may not describe the later response. Check geometric imperfections and conductor rotation when they affect contact.

For stability, evaluate the admissible mode about the current loaded equilibrium and follow the relevant nonlinear response. The local force-component calculation alone cannot establish a telescopic critical load.

Release the motion mechanism

The handover should identify the helical geometry, force components, restraint model and controlling relative displacement or rotation. State whether the result is whole-winding translation, local telescopic movement or section tilting.

Use the identified motion to target the restraint that carries it. Strengthen the overall end path where translation controls, and improve the verified interturn path where relative movement governs the local gap or contact condition.

Hermann A. Haus and James R. Melcher. Electromagnetic Fields and Energy. 1989, Chapter 11, Lorentz-force and electromechanical force treatment.

IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]

Carry uncertainty in the measured model inputs and responses into the comparison, including correlated contributions. [2]

References

[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.

[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.

Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing