Include cross-section rotation and the actual load line when assessing conductor tilting. Track their force-and-moment balance at the spacer contact alongside circumferential bending, so the active contact and rotational restraint remain visible.
The controlling artifact is a cross-section force-and-moment balance tied to the actual spacer contact, together with the circumferential span model.
Define the rotation separately from span bending
Let φ describe rotation of the conductor cross-section about its local longitudinal direction. Let w(s) describe bending along the circumferential span between spacers. These are different degrees of freedom and can interact through the support reactions.
A radial offset of an axial load produces a moment about the conductor’s longitudinal direction. The moment is M = Pe when resultant load P acts at eccentricity e from the center of the represented support width.
Relate span bending to moment and curvature. Retain cross-section rotation and unilateral support contact as separate coordinates and equations.
Retain conductor dimensions, composite or strand behavior, torsional restraint and the position of neighboring contacts. The support can restrain rotation only if its actual reaction path develops the corresponding moment.
Start with a transparent contact model
Consider a rigid cross-section on a linear compressive foundation. Its radial support width is b and contact depth is d. Take x = 0 at the support center and use a pressure profile linear in x while full contact remains.
Force and moment equilibrium give:
p(x) = P/(bd) + 12Pe x/(d b³).
The two edge pressures are P/(bd)[1 ± 6e/b]. Because an unbonded interface cannot sustain tensile pressure, this full-contact solution is admissible only while |e| ≤ b/6.
The b/6 condition is a contact-state limit in this model. It is not the same as the b/2 condition at which the load resultant reaches the support edge, nor is it a conductor yield or torsional-instability criterion.
A local eccentricity calculation
Assumption: Choose P = 1,000 N, b = 10 mm and d = 20 mm. The centered average pressure is 5 MPa.
At e = 1 mm, the full-contact edge pressures are 2 and 8 MPa. At e = 2 mm, the same algebra predicts −1 and 11 MPa. The negative value means the full-contact assumption has failed; it should not be reported as a physical tensile reaction at an unbonded spacer.
For e > b/6 with the resultant still inside the support, the same unilateral linear-foundation idealization gives a triangular pressure patch of width:
a = 3(b/2 − e),
with p_max = 2P/(ad). Its centroid lies a/3 inward from the loaded edge, so the prescribed moment is retained.
| Original eccentricity case | Contact state | Contact width | Maximum pressure |
|---|---|---|---|
| e = 1 mm | Full contact | 10 mm | 8.000 MPa |
| e = 2 mm | Partial triangular contact | 9 mm | 11.111 MPa |
| e = 4 mm | Partial triangular contact | 3 mm | 33.333 MPa |
As e approaches 5 mm, the patch width tends to zero in this idealization. The resulting pressure growth signals the loss of a feasible finite-pressure support state, rather than a usable prediction beyond the model’s contact range.

Compare bending, contact loss and rotation
Evaluate the span’s bending response with the actual spacer reactions. Separately evaluate φ, the associated moment and the active contact width. A conductor may remain below a selected bending stress limit while a support edge unloads and the rotational restraint changes.
If another interface or bonded layer carries tension or moment, include it explicitly. The unilateral b/6 result then no longer describes the complete restraint by itself. If insulation compresses nonlinearly, replace the linear foundation with its supported constitutive behavior.
A static eccentricity calculation also does not establish a dynamic tilting threshold. That assessment requires the loaded tangent response, inertia, changing contact and the actual force history. Track the local rotation and pressure rather than only the maximum beam displacement.
Use the as-built load line
Load eccentricity can come from a support offset, conductor geometry, neighboring force distribution or a deformed contact. Reference e to the active support region in the assembled drawing, not to a nominal winding center that does not carry the reaction.
Check whether the effective contact width changes with assembly or loading. Record the conductor and spacer identities, contact location and restraint assumed between adjacent spans. A broad nominal spacer does not establish full-width load transfer if only an edge is engaged.
Release the local mechanism
The handover should identify the bending limit, cross-section rotation, contact state and pressure maximum separately. State which quantity controls and which restraint carries its moment.
Target the controlling path: reduce load eccentricity, restore effective contact or improve the restraint carrying the rotational moment. Recheck local pressure and span bending together after the change, using the assembled support geometry.
David Roylance. Stresses in Beams. MIT, 2000, bending moment, curvature and normal-stress treatment.
IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]
Retained preload and joint stiffness determine how a clamped load path responds and when compression is relieved. [2]
References
[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.
[2] Jeffrey A. Chambers, NASA, Preloaded Joint Analysis Methodology for Space Flight Systems, NASA TM-106943, December 1995.