Compensate the documented temperature-dependent model term while preserving the change the FRA study must detect. Retain the raw curve and apply a parameter-based correction that can be checked against both a thermal baseline and an independent geometry perturbation.
Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.
Resistance drift can change damping and move a visible peak even when inductance and capacitance remain fixed. A useful compensation model therefore distinguishes a shifted magnitude maximum from a changed underlying reactive parameter.
Establish the temperature baseline first
Record the winding temperature estimate, its spatial meaning, the test chronology and the reference temperature. Keep the terminal conditions and lead arrangement consistent. A tank or ambient temperature is not automatically the winding temperature relevant to the modeled resistance.
Identify the conductor impedance and the damping terms being corrected over the study band. Applying a direct-current factor to every broadband damping term requires a separate physical model.
Retain the resistance coefficient, temperature difference, affected terms and their uncertainty in the compensation model. Keep any covariance among these inputs when evaluating the corrected curve.
If temperature also changes a material property that affects capacitance, include that contribution separately when supported. Do not force all temperature effects into resistance or label all remaining response drift as geometry.
Resistance alone can move the peak
Use an original series R–L branch feeding C, with capacitor-voltage transfer:
H(s) = 1/(1 + sRC + s²LC).
Let L₀ = 1 mH, C = 10 nF and select R₀ = 126.491106 Ω, giving damping ratio ζ₀ = 0.2. The undamped frequency is f_n = 1/[2πsqrt(LC)], while this transfer’s magnitude peak is:
f_peak = f_n sqrt(1 − 2ζ²),
where ζ = (R/2)sqrt(C/L).
Assume a documented illustrative baseline R(T) = R₀[1 + 0.004(T − T₀)]. A 50 K increase gives a 20% resistance increase. The coefficient is an original assumption for the calculation, not a specified material constant for all windings.
The reactive product LC remains unchanged, so f_n stays at 50.329 kHz. Nevertheless, ζ increases from 0.2 to 0.24 and the magnitude peak moves downward. A rule that equates every peak shift with a change in winding geometry would misinterpret this temperature-only case.
Preserve a simultaneous geometry change
Now combine the same resistance increase with L = 1.1L₀, holding C fixed. This perturbation isolates the effect of a 10% inductance change; obtain the real movement-to-inductance relation from the geometry model.
The changed L lowers the undamped frequency. Correcting the resistance should remove the assumed thermal contribution while retaining this LC change.
| Constructed case | Damping ratio ζ | Undamped frequency | Magnitude-peak frequency |
|---|---|---|---|
| Reference | 0.200000 | 50.329 kHz | 48.274 kHz |
| Temperature only | 0.240000 | 50.329 kHz | 47.342 kHz |
| Temperature plus L change | 0.228831 | 47.987 kHz | 45.405 kHz |
| After resistance correction | 0.190693 | 47.987 kHz | 46.209 kHz |
After the resistance correction, the combined case still differs from the original reference. That residual is the intended behavior of a compensation that preserves the modeled reactive change.

Correct the identified temperature-dependent parameter
For this exact topology with known, unchanged C and known resistance increment ΔR, the measured-model inverse transfer is:
H_meas⁻¹ = 1 + s(R₀ + ΔR)C + s²LC.
Define:
H_corr = 1/[H_meas⁻¹ − sCΔR].
Only the resistance-dependent coefficient is removed. The s²LC term remains as measured by the stated model, so the L change survives. In the temperature-only case the correction recovers the reference response exactly.
This is a topology-specific transformation. A multiport winding model requires a supported parameter correction in its own network or rational representation. A generic scalar transformation applied to arbitrary FRA traces can remove or introduce features unrelated to the actual temperature mechanism.
Test whether compensation preserves the anomaly
Validate the correction against a temperature-only reference series and a separate controlled parameter-change case. Compare the complete complex responses before and after correction. Check peak location, damping and the fitted reactive parameters together.
Propagate uncertainty in temperature and the resistance coefficient into the compensated result. If the inferred anomaly is smaller than the supported compensation uncertainty, report that separation has not been established. For a simultaneous capacitance change, the fixed-C equation above must be revised rather than applied mechanically.
Keep the raw response and temperature record alongside the corrected result. A reviewer should be able to reconstruct which term changed and why. The original trace remains evidence of the measurement conditions, even when a compensated trace is used for comparison.
Make the diagnostic decision explicit
The release statement should identify the temperature-dependent parameter model, show that it explains the baseline drift, and demonstrate that the relevant independent geometry perturbation survives the correction. A correction that merely improves similarity to a reference fails that test.
Report the response difference remaining after the supported thermal contribution is removed. Tie that result to the corrected parameter, retained reactive terms and propagated uncertainty so the designer has a defined change to investigate.
Gustavsen and Heitz show that fitted multiport accuracy depends on terminal conditions and the visibility of small modes. Validate the response used for the engineering decision under its actual terminal loads. [1]
NIST TN 1297 provides the measurement-uncertainty basis for retaining influence quantities and covariance. Apply that bookkeeping to the declared inputs and comparison metric rather than treating numerical agreement as a measurement uncertainty. [2]
IEC 60076-18 addresses frequency-response measurements and measurement equipment for transformers in factory and site conditions. Record the actual test connections and instrument conditions with each curve. [3]
References
[1] B. Gustavsen and C. Heitz, Modal Vector Fitting: A Tool for Generating Rational Models of High Accuracy with Arbitrary Terminal Conditions, 2008, DOI:10.1109/TADVP.2008.927810.
[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.
[3] IEC, IEC 60076-18:2012, Power transformers — Part 18: Measurement of frequency response.