Retain earth capacitance when modeling a floating tertiary. Its reference paths establish common-mode voltage; a floating short removes terminal differential voltage while leaving that common voltage to be solved from the network.
Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.
Preserve both the internal winding network and the external terminal constraints. The correct question is which currents are prohibited by the external connection, not which electrical elements can be deleted.
Define the external constraints
For two represented tertiary terminals A and B, an externally open condition sets their external current injections to zero. It does not prohibit internal current through winding inductance, resistance or capacitance.
A floating short between A and B imposes v_A = v_B while allowing current redistribution through the short. Grounding both terminals additionally imposes that common voltage equal to the reference. These are different network constraints.
For a delta-connected tertiary, retain the closed internal branches even if no external load is connected. Internal circulating behavior and terminal common-mode behavior require different parts of the model. The connection diagram should identify what is externally floating and what remains internally connected.
Retain the capacitance reference
Represent capacitance to earth and between winding groups with the same conductor reference as the rest of the circuit. Preserve charge balance, mutual terms and electrostatic energy.
Separate differential voltage v_d = v_A − v_B from the defined common voltage v_c = (v_A + v_B)/2. Their insulation consequences belong to different interfaces. A small terminal-to-terminal voltage can coexist with a substantial voltage to grounded structure.
A model without a common-mode reference may need an explicit charge constraint or gauge treatment. Adding an arbitrary large resistor merely to make the equations solvable can create an unintended physical path. Determine what reference or charge state is represented before changing the circuit.
An original two-terminal broadband example
Use a 1 MHz sinusoidal phasor drive V_H = 1,000 V. Couple H capacitively to A through 100 pF and to B through 20 pF. Retain A-to-reference capacitance 30 pF, B-to-reference capacitance 10 pF, and A-to-B capacitance 40 pF.
A linear branch between A and B has R = 20 Ω and L = 1 mH. This original network isolates electrical coupling; no magnetic excitation from the driven winding is included.
For externally open A and B, their nodal equation is:
[jωC + (R+jωL)⁻¹D]v = jω[100, 20]ᵀ pF × V_H,
where C = [[170, −40], [−40, 70]] pF and D = [[1, −1], [−1, 1]].
Solving gives:
v_A = 762.005 + j0.0248 V
v_B = 697.977 − j0.1074 V.
The terminal-to-terminal magnitude is 64.029 V, while the magnitude of the defined common voltage is 729.991 V. The externally floating winding therefore has a definite voltage to reference through its retained capacitances.
Compare three terminal states
With a floating short, v_A = v_B and the joined potential follows the total drive and reference capacitances:
v_A = v_B = [120/(120+40)]V_H = 750 V.
Grounding the joined terminals instead gives zero common voltage. The following values belong to the specified network and frequency:
| External tertiary state | Magnitude of v_A − v_B | Magnitude of (v_A + v_B)/2 |
|---|---|---|
| Both terminals externally open | 64.029 V | 729.991 V |
| A and B joined, still floating | 0 | 750.000 V |
| A and B joined and grounded | 0 | 0 |
If the 30 pF and 10 pF earth capacitances are deleted from the open-terminal model, both terminals instead follow the single driven conductor at 1,000 V. That change is caused by removing reference paths, not by a change in the physical tertiary connection.

Carry the constraint into the complete transformer model
A full broadband model should add the relevant magnetic coupling, distributed winding elements, losses and connections. Keep the same terminal-state definitions when comparing cases. An ideal short can permit induced current that this purely electrical-coupling benchmark does not excite.
Sweep frequency and external loads while monitoring both common-mode and differential voltages. Record internal group voltages separately if they control insulation. An externally floating terminal does not establish that every internal section has the same potential.
Gustavsen and Heitz’s original modal-fitting analysis shows why current, voltage and hybrid terminal conditions can expose different model errors. Validate the floating and constrained responses that the study actually uses, rather than accepting only one fitted port configuration. [2]
Release a clear tertiary-state contract
The handover should identify the internal connection, externally open terminals, joined conductors, earth paths, initial-charge or reference treatment and observation quantities. Retain the source of each parasitic capacitance and the supported frequency band.
Release the tertiary model with its common-mode reference, differential constraint and internal connection explicit. Apply that state contract consistently to the open, floating-short and grounded comparisons, and report both voltage observables with the supported frequency band.
Smolić and Klajn derive the conductor charge–potential matrix with its reference and domain conditions. Preserve that reference when interpreting charge, energy and any reduced network. [1]
Gustavsen and Heitz show that fitted multiport accuracy depends on terminal conditions and the visibility of small modes. Validate the response used for the engineering decision under its actual terminal loads. [2]
References
[1] I. Smolić and B. Klajn, Capacitance Matrix Revisited, 2021, DOI:10.2528/PIERB21011501.
[2] B. Gustavsen and C. Heitz, Modal Vector Fitting: A Tool for Generating Rational Models of High Accuracy with Arbitrary Terminal Conditions, 2008, DOI:10.1109/TADVP.2008.927810.