Define simulated solar loading by where external heat enters and which temperature it must represent. Surface irradiation, internal heating and a warmer room impose different heat paths, so select the simulation against the design question. [1]
A thermal qualification using simulated sunlight therefore needs a stated equivalence target. It might assess enclosure surface temperature, cooling-air intake, oil temperature or a particular internal component. One arrangement need not reproduce all of them equally well.

Specify absorbed radiation on the actual surfaces
For a simplified uniformly illuminated surface, absorbed power is Qabs = αGA, where G is irradiance incident on that surface, A is the illuminated area and α is the absorptance appropriate to the source spectrum and surface condition.
With illustrative incident irradiance800W/m², area2m² and absorptance0.70, the absorbed input is1.12kW. The irradiance here is already defined on the selected surface; it is not a beam-normal value awaiting an additional incidence-angle conversion.
Solar absorptance and thermal-infrared emissivity describe different spectral properties. A lamp can also have a different spectrum from sunlight. Equal total incident irradiance does not necessarily produce equal absorption if the surface’s absorptance varies with wavelength. Record the relevant surface finish and source characteristics.
Map the proposed simulation to the heat path
| Simulation input | What it can represent | What remains to establish |
|---|---|---|
| Radiation applied to selected exterior surfaces | Absorbed exterior heat where spectrum and distribution are suitable | Surface absorption, spatial uniformity, exposure orientation and surrounding airflow |
| Raised ambient air temperature | A changed convective cooling boundary | Whether surface heating and directional gradients are represented |
| Internal electrical or auxiliary heating | Heat generated within the selected internal region | Its relation to exterior heating and the intervening heat-transfer paths |
| Localized surface heaters | A controlled imposed heat input on particular surfaces | Contact transfer and temperature distribution compared with absorbed radiation |
Measure the boundary as well as the response
Document the irradiance distribution or other applied heat input, surface temperatures and cooling-air conditions. Avoid using the same internal-temperature result both to tune the imposed input and to claim that the input is independently equivalent.
Check whether the setup changes airflow around radiators or heats nearby structures that then radiate towards the transformer. Shadows and exposed area can also change with orientation. The intended reference exposure should be described rather than inferred from a lamp’s nominal electrical power.
Define the liquid-immersed transformer cooling mode, measured temperature quantity and represented duty with the governing temperature-rise method; a separate diagnostic model does not supply an unviewed test limit. [2]
Close the imposed absorbed-power boundary
In that assumed 800 W/m², 2 m² exposure, changing absorptance from 0.70 to 0.50 lowers absorbed power from 1.12 to 0.80 kW, a 28.57% reduction. Verify spectrum, finish and spatial exposure before declaring equivalence from equal nominal lamp power.