Evaluate press-ring flexibility through the pressure it transfers to the winding. Rod positions, ring stiffness and support response shape that distribution; compare the flexible and rigid models using the active contact and local design limits.
Check deflection and compressive contact together. A model that assigns tensile reaction to an unbonded interface has passed beyond its assumed contact state.
Keep the rod-to-winding load path
Map tie-rod positions, load introduction areas, ring thickness, winding support regions and gaps. Include the ring’s bending and torsional stiffness where the geometry requires them. A load at one rod can be transferred through neighboring ring sectors before reaching the winding.
For a local straight-sector approximation, elastic curvature equals bending moment divided by EI. Integrating equilibrium and curvature with the stated boundary conditions gives the reference deflection below.
A complete circular ring or plate retains curvature, finite width, holes, supports and the actual connection pattern. The local beam approximation below isolates a contact issue without substituting for that assembled geometry.
An elastic-foundation reference
Consider an infinite straight beam with bending stiffness EI on a bilateral linear foundation of stiffness k per unit length per unit displacement. Let downward deflection w be positive and apply a concentrated downward force P at x = 0.
The governing equation is EI d⁴w/dx⁴ + kw = Pδ(x). Its symmetric decaying solution is:
w(x) = [P/(8EIβ³)] exp(−β|x|)[cos(β|x|) + sin(β|x|)],
where β = [k/(4EI)]^(1/4).
The foundation reaction per unit length is q_f = kw. “Bilateral” means this reference foundation can pull as well as push. That makes the solution mathematically convenient, but it must be checked before representing an unbonded winding contact.
Find where the contact assumption fails
The first zero of cos u + sin u for positive u is u = 3π/4. The reference solution therefore predicts a negative foundation reaction beyond:
x₀ = 3π/(4β),
until its next sign change. An unbonded compressive interface cannot supply that tensile reaction. The negative region identifies where the bilateral contact assumption must be replaced and the equilibrium solved again.
It does not directly establish the final opening boundary of a unilateral model. Removing the tensile reaction redistributes both deflection and load.
A numerical load-spreading scale
Assumption: Choose original parameters EI = 1,000 N·m², k = 100 MN/m² and P = 1,000 N. Then:
β = 12.574334 m⁻¹, so the characteristic length 1/β is 79.527 mm.
The center deflection is w(0) = 0.062872 mm, and the peak reference reaction is q_f(0) = 6287.167 N/m. The first zero occurs at x₀ = 187.381 mm.
At βx = 3, the normalized deflection is exp(−3)(cos 3 + sin 3), which is negative. The corresponding predicted reference reaction is approximately -265.714 N/m. That value is a model-consistency flag, not a physical tensile winding-contact pressure.

Compare rod spacing with the flexible load path
In the bilateral reference, multiple loads can be superposed. Their spacing relative to 1/β controls how strongly the local deflection and reaction patterns overlap. A finite ring also imposes its own end, symmetry and connection constraints.
Use the actual rod pattern in the assembled model. Evaluate pressure near load introduction, between rods and at changes in ring section or winding support. The mean pressure calculated from total force and nominal area cannot identify those local peaks or unloaded regions.
A thicker or stiffer ring changes the bending length scale, but it can also transfer force into a different contact region. Judge the change through the resulting pressure and active contact rather than through thickness alone.
Re-solve with compressive contact
Represent an unbonded interface with nonnegative pressure and the appropriate separation condition. Include initial gaps and supported insulation-compression behavior. Preserve the total applied load while allowing the active contact region to change.
Compare the flexible model with the rigid-plate model under the same rod loads and support geometry. Record maximum and minimum active pressure, ring deflection, open regions and the force balance. If the rigid assumption misses a controlling pressure concentration or contact loss, retain the ring flexibility in the released model.
Check that contact discretization and ring mesh refinement stabilize those quantities. A small displacement error can move a contact boundary and change a local pressure peak, so displacement convergence alone is not sufficient.
Release a load-distribution conclusion
The handover should identify the rod pattern, ring stiffness, foundation or winding-support law, gap assumptions and active contact map. Relate local pressure limits to the actual material and assembly evidence used by the design.
Report where the rod loads reach the winding, the active contact regions and their controlling pressures. Accept the rigid-plate simplification when it preserves those quantities to the required accuracy under the same assembled load case.
David Roylance. Beam Displacements. MIT, November 30, 2000, load integration, curvature and boundary-condition treatment.
IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]
Retained preload and joint stiffness determine how a clamped load path responds and when compression is relieved. [2]
References
[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.
[2] Jeffrey A. Chambers, NASA, Preloaded Joint Analysis Methodology for Space Flight Systems, NASA TM-106943, December 1995.