Before using a core model in an open-phase study, challenge the magnetic coupling that a healthy balanced test can leave hidden. A zero-sequence excitation screen can reject an unsuitable model structure; a complete open-phase prediction still needs the actual winding connection, source, loading and nonlinear excitation response.

Identify the shared magnetic return
For three-limb construction, uncompensated zero-sequence flux returns outside the main laminated path. Additional low-reluctance return limbs or separate single-phase cores create different magnetic constraints. The SEL fundamentals paper derives this distinction from ampere-turn balance [1]. A vector-group label and positive-sequence leakage impedance do not identify that return network.
Record the core construction, any closed delta, neutral paths and relevant magnetizing characteristics. A closed delta can supply compensating ampere-turns and change the excitation being observed. The open-phase paper also shows why load and fault conditions matter to terminal-voltage indications [2]. Keep those electrical effects separate from the core-model screen.
Hold the section fixed and change the coupling
Catalogue input: nominal sheet gauge 0.23 mm [3]. Assumptions for a linear magnetic-circuit fixture: 1,000 active sheets, 100 mm strip width, 100 turns per limb, negligible winding drop and losses, and 50 Hz sinusoidal excitation. Steel section is 0.0230 m². Each limb has reluctance Rℓ = 1,000 A/Wb; the shared external return has R₀ = 20,000 A/Wb. These reluctances are constructed test inputs, not identified transformer parameters.
For limb k, N iₖ = Rℓ Φₖ + R₀(ΦA + ΦB + ΦC). Under balanced positive-sequence flux, the sum is zero, so each phase has L₁ = N²/Rℓ = 10.00 H. Three uncoupled 10 H inductors would therefore reproduce this particular balanced response while omitting the shared return.
Under equal in-phase zero-sequence excitation, ΦA = ΦB = ΦC. The coupled model instead gives L₀ = N²/(Rℓ + 3R₀) = 0.163934 H. Apply an assumed 10.00 V RMS per winding on that common-mode basis:
| Model | Per-phase zero-sequence inductance | Per-phase RMS current |
|---|---|---|
| Shared-return reference fixture | 0.163934 H | 0.19417 A |
| Uncoupled model fitted to L₁ | 10.00 H | 0.003183 A |
Current follows I = V/(2πfL). The uncoupled model underpredicts this fixture’s zero-sequence current by a factor of 61, despite matching its balanced inductance. Both models see the same imposed voltage and steel section: Bpk = V/(4.44fNA) = 0.01958 T. Changing sheet count to adjust B would not repair the missing coupling.
Use the screen to reject a structure, then validate the study
Reject the uncoupled representation for this declared reference network. The fixture demonstrates a specific non-identifiability: agreement under balanced excitation does not determine zero-sequence behaviour. It supplies no asset-specific open-phase voltage or relay setting.
For the installed transformer, obtain an independently supported zero-sequence response or magnetic-return model, then compare phase-voltage magnitudes, angles and excitation waveforms for the actual open-phase cases. Preserve source impedance, load, delta circulation and instrument burden. Use nonlinear material behaviour where the represented excursion requires it [1] [2].
Sheet gauge, active count, joint registration, gaps and clamp state define the manufactured path. Retain them with the measured excitation data; matching catalogue material alone does not identify the assembled coupling.
References
- B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
- J. LaBlanc, Y. Shah and J. Aultman, Schweitzer Engineering Laboratories, Revisiting Open-Phase Detection for Fuse-Protected Power Transformers, 2024.
- Nippon Steel Corporation, Grain-Oriented Electrical Steel Sheets, catalogue D004je, April 2020, specification tables, size tolerances and Annealing by Customers.