Trace the remaining energized paths after an external primary conductor opens on a delta transformer. The surviving source can feed a winding directly and other windings through their connected path, leaving secondary voltages whose pattern depends on connection and load.

Draw the opened conductor outside the winding connection
Identify the conductor break, the remaining source terminals and each winding’s polarity. Distinguish a primary line conductor from an individual delta winding branch. The intact delta connection can sustain internal coupling after one external conductor opens; opening a winding branch is a different circuit. [1]
Map the secondary winding associated with each primary branch and the actual voltage-transformer terminals. Include vector group and phase sequence. A sketch with three unnamed coils can conceal a different association between the open conductor and the measured phase.
Keep phase and line voltage bases separate
For the ideal, balanced Dyn example in the SEL open-phase paper, choose the directly supplied secondary voltage Vc as 1∠0° pu on a phase-voltage base. The other two are Va = Vb = 0.5∠180° pu [2]. These conditional ideal-circuit values do not predict every transformer at no load.
| Observation in that example | Calculated relationship | Interpretation |
|---|---|---|
| Vc | 1 pu on the phase-voltage base | One nominal phase reading survives |
| Va and Vb | Both −0.5 pu relative to Vc | Nonzero readings have abnormal magnitude and relative angle |
| Vab | Va − Vb = 0 | The two phases no longer supply their healthy line voltage |
| Vbc and Vca magnitudes | 1.5 phase-base pu, or 1.5/√3 ≈ 0.866 line-base pu | Base conversion matters when comparing relay quantities |
Recalculate when the loads differ
The series-associated windings in the simplified circuit share the remaining source according to the represented impedances. Unequal load magnitudes or angles change that division. A voltage pattern derived for balanced passive loads must be revisited for a different load distribution, a permanent fault or another source on the secondary. [2]
At very low load, retain magnetizing branches and the actual magnetic construction where they determine the result. An ideal equivalent circuit explains a mechanism; it does not establish all lightly loaded terminal voltages of a physical unit.
Review evidence at named points
Record three phase voltages, their relative angles, relevant currents and the measurement locations with the topology. Distinguish actual conductor status from a switch indication or an inferred voltage state. A meter downstream of a coupled winding answers a different question from continuity of the upstream conductor. [2]
Use the named-terminal voltage, angle and current map in offline model and protection review. Compare the observed surviving voltages with the reconstructed winding paths and source state, then verify conductor status through its own independent evidence.
References
- B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
- J. LaBlanc, Y. Shah and J. Aultman, Schweitzer Engineering Laboratories, Revisiting Open-Phase Detection for Fuse-Protected Power Transformers, 2024.