Solve voltage displacement and joint heating together for a finite neutral impedance. The deteriorating return path changes load voltages and neutral current, which in turn determine the joint’s electrical dissipation. [1]

Add the actual return impedance
For a simplified linear star load, define source phase phasors Ep, load admittances Yp and neutral admittance Yn between the load star point and source neutral. The nodal relation is Vn = Σ(YpEp)/(ΣYp + Yn). Neutral current is In = YnVn, with sign set by the chosen reference direction.
For a purely resistive neutral joint Rn, its local electrical dissipation is |In|²Rn using RMS current. The current changes when Rn changes because the load voltages change. Holding the original current fixed is only a separate sensitivity calculation.
Compare finite and open states
Use assumed stiff-source phase voltages of 230 V separated by 120°, and resistive loads of 10, 20 and 40 Ω. Omit other return paths, line impedance and thermal feedback for this illustration. [1]
| Assumed neutral-joint state | Star-point magnitude | Neutral-current magnitude | Joint dissipation |
|---|---|---|---|
| 2 Ω | 22.54 V | 11.27 A | 253.98 W |
| 10 Ω | 55.32 V | 5.53 A | 306.03 W |
| Ideal complete opening | 86.93 V | 0 A through the removed path | No dissipation assigned to an absent model branch |
The last row does not imply a harmless open neutral. It shows that the local joint-power trend is not indefinitely proportional to resistance. Real deterioration, arcing and changing contact geometry are outside this passive resistor model.
Match the electrical and thermal observations
Register joint location, measured voltage drop, neutral current and load condition on a common time basis. A hot joint can have multiple causes; temperature alone cannot separate contact resistance from poor cooling or another nearby heat source. A small voltage displacement at one balanced load state cannot establish a sound connection. [1]
To predict temperature, add the heat-transfer path, thermal mass, ambient condition and relevant temperature-dependent contact behaviour [2]. Electrical watts alone do not supply temperature rise. Define the measurement boundary and uncertainty before assigning a resistance change to the joint [3].
Keep this fault path distinct from designed grounding
The model concerns an unintended impedance in a load-neutral connection. A specified neutral-grounding resistor has a different location, function and rating basis. Naming both neutral resistance does not make their circuits interchangeable. [4]
Use the load sweep and observed joint condition to target the engineering investigation. Match electrical readings in time, then add the supported thermal path to assess local temperature. Keep an unintended load-neutral defect separate from the specified grounding-device model.
References
- J. Campos, G. Freire, A. Babu, S. Keddar and I. Abdulhadi, Detection of broken neutral conductor in LV networks to ensure customer safety, CIRED Paper 1078, 2025, DOI: 10.1049/icp.2025.2212.
- U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.
- B. N. Taylor and C. E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994, sections 5 and 6.
- T. Novak, J. Basar, J. Sottile and J. L. Kohler, The Effects of Cable Capacitance on Longwall Power Systems, IEEE Transactions on Industry Applications 40(5), 2004; DOI: 10.1109/TIA.2004.834025.