Rank thermal tap candidates by their winding-current paths, loss distribution and local cooling. The lowest-voltage tap is an important candidate at fixed apparent power, while the controlling hot spot depends on the energized sections and their heat paths. [1]
Changing tap position can change the energized conductor length, current path, leakage-field distribution and local cooling demand. A defensible screening process keeps those changes with the current calculation.

Establish the operating duty at every candidate tap
Use the specified voltage and apparent-power duty to determine winding currents through the actual connection model. For a balanced sinusoidal three-phase terminal, S = √3VI is a useful relationship, but it does not replace the winding connection and harmonic-current calculation.
Identify the conductors and tap contacts carrying those currents. Check which winding sections are in circuit and which components change duty. The maximum terminal current may not be the current that limits a particular tap section or internal lead.
Current and conductor loss can rank the taps differently
Consider two illustrative one-phase conductor paths. Their resistances are specified at the same reference temperature so the comparison does not mix thermal states. PathA carries100A through0.10Ω; pathB carries90A through0.14Ω.
| Candidate | Current | Reference resistance | I²R loss |
|---|---|---|---|
| Tap conditionA | 100 A | 0.10 Ω | 1,000 W |
| Tap conditionB | 90 A | 0.14 Ω | 1,134 W |
The lower-current path has13.4% higher conductor loss in this selected comparison. The example establishes no actual transformer ranking. Final thermal calculations need the appropriate hot resistance, additional losses and a consistent operating model.
Screen the local thermal path as well as the watts
Map the loss changes to winding sections, leads, contacts and nearby structures. Include additional winding and structural losses where the design model supports them. Changing leakage fields can shift a local heat source without producing a proportionate change in total loss.
Compare the corresponding cooling paths. A hotter candidate may be a poorly supplied section rather than the section with the largest calculated watts. A cooling arrangement that performs well at one tap should not be assumed to maintain the same local distribution at another.
Use local thermal paths to test the loss ranking. DOE’s heat-transfer account relates heat flow to resistance and temperature difference [2]. Equal total watts do not imply equal local rise when heat paths differ.
Use the loss ranking to select verification
Continue the assumed 1,000 W and 1,134 W paths. Assume independent steady lumped nodes, 30 °C cooling boundaries and effective resistances of 0.020 and 0.012 K/W, with no mutual coupling. Their temperatures are 30 + 1,000 × 0.020 = 50.0 °C and 30 + 1,134 × 0.012 = 43.61 °C. The lower-loss path is 6.39 K warmer. Target path A for verification in this fixture; real tap selection needs measured or validated local heat paths and coupling.
Select a verification duty with an explicit reason
Rank candidate tap conditions using the specified current envelope, loss map and thermal analysis. Identify uncertainties that could reverse the ranking. Use targeted measurements on relevant regions and the governing test procedure to verify the proposed limiting condition.
References
- IEC, IEC 60076-2:2011, Power transformers — Part 2: Temperature rise for liquid-immersed transformers.
- U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.