Comparing Star-Delta and Zigzag Internal Grounding Duty

  • Chenfan Power

Compare star-delta and zigzag grounding designs through their internal current paths. The same system neutral-current duty can produce different conductor losses, magnetic return paths and local heating. Put both designs on the same supplied duty and section-current basis. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Set one common case: operating voltage and frequency, neutral-current waveform, duration, pre-fault thermal state, external neutral impedance and any simultaneous auxiliary load. If one design has an auxiliary load and the other does not, the thermal comparison already contains a different task.

Comparing Star-Delta and Zigzag Internal Grounding Duty: technical review table
Follow the currents through each connection

Follow the currents through each connection

For a symmetrical zero-sequence component, each grounded-star phase carries I0 = IN/3. A closed delta winding supports internal circulating current even with no external delta load. In an ideal magnetic balance, NyI0 + NdIδ ≈ 0 when current-reference signs are chosen consistently. Ny and Nd are turns per corresponding winding section; currents are in amperes. The circulating-current magnitude is therefore approximately (Ny/Nd)|I0|, with magnetizing current neglected.

In a symmetrical zigzag, each phase path contains two series sections on different limbs. Both sections carry I0. Opposing sections from different phases provide the limb ampere-turn balance. The delta circulation of the star-delta unit and the cross-limb section currents of the zigzag unit are different mechanisms.

Internal quantityGrounded star with closed deltaZigzag
Neutral leadININ
Main series pathI0 in each star phaseI0 through both sections of each phase
Additional magnetic balanceReferred delta circulating currentOpposing cross-phase sections on each limb
Continuous heating to examineStar conductors, delta loop and closure jointsAll six sections and their series junctions
Core representationActual limb and return-path geometryActual limb geometry and section placement

Compare losses on the correct section-current basis

For an elementary resistive loss estimate, sum Isection²Rsection over the identified conductors, using RMS current in amperes and resistance in ohms at the relevant temperature. The result is watts. A zigzag estimate contains six section terms. A star-delta estimate contains its star terms and the delta terms at the delta circulating current, plus the closure connections.

The number of terms alone proves nothing about total loss. Turn counts, conductor dimensions, mean turn lengths and resistance differ between constructions. Harmonic and stray losses also require their own treatment. A delta without an external load is not a delta without internal heating.

Match the magnetic and thermal assumptions

Core construction cannot be inferred from the connection label. Three-limb, additional-return-limb or single-phase-bank constructions can create different external flux paths and local structural heating. Determine which magnetic model applies before attributing a nonlinear impedance difference to the winding connection alone.

Request section-current maps and loss allocations for the matched duty. Compare the hottest starting state, short-time temperature rise and repeated-event recovery to identify the conductor or magnetic path that controls each design.

Compare both internal conductor systems numerically

Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].

Assume 300 A RMS neutral current and pure zero sequence at 50 Hz. For a zigzag with six 0.020 Ω sections, copper loss is 6 × 100² × 0.020 = 1,200 W. For a star-delta design with unity relevant turns ratio, three 0.015 Ω star sections and three 0.030 Ω delta sections give 1,350 W. The latter is 12.5% higher for these assumed resistances. Select from the actual section resistances and hotspot evidence, rather than connection names.

References

  1. D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
  2. IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.