  • Chenfan Power

Bypassing an external grounding impedance changes the settled neutral potential, fault current and internal winding voltage drops. Assess those changes together, then calculate the switching interval separately for the actual terminals and insulation interfaces. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Identify the neutral terminal N, the local grounded structure G and any remote reference E. A device connected from N to G experiences VN − VG. It does not necessarily experience VN − VE, especially when fault current raises the local grounding-system potential.

Neutral Voltage When Grounding Impedance Is Bypassed: technical review table
Draw the two settled circuits on the same basis

Draw the two settled circuits on the same basis

For a simple neutral path, VN − VG = INZn, where IN is the neutral-current RMS phasor in amperes and Zn is the external neutral-path impedance in ohms. The voltage is in volts. Before bypass, Zn includes the intended grounding device and associated connection. After bypass, use the actual bypass lead and contact impedance rather than replacing the whole return network with an unexplained ideal ground.

The transformer’s per-phase zero-sequence impedance remains a separate element. In its sequence network, the external neutral impedance appears with the factor appropriate to the phase-current basis, commonly 3Zn when neutral current is 3I0. Changing Zn therefore changes both IN and the neutral drop. Holding the old fault current fixed while calculating the new circuit can give a misleading comparison.

Circuit stateNeutral potential modelAdditional voltage question
Grounding impedance in circuitIN through the identified device and leadsDevice terminals, neutral insulation and local reference
Transition in progressTime-dependent switch, capacitance and inductive networkInitial stored energy and contact behavior
Bypass establishedRecalculated IN through bypass connectionHigher winding current drops and bypass lead duty

Keep the switching interval out of a phasor shortcut

Inductor currents and capacitor voltages retain state across a switching event. A settled calculation in which VN immediately becomes zero cannot reproduce that state transfer. The transition model needs the actual switch topology, operating timing, winding-to-ground and interwinding capacitances, leakage paths and any connected protection or measurement equipment.

For each model node, record what the node was connected to before the transition and what connection becomes available afterward. A disconnected measurement circuit or a bypass branch placed on the wrong side of a CT can affect the evidence used to interpret the event even if the final neutral bond is intact.

The SEL paper shows that changing grounding-source availability can produce voltage transients and alter protection response. Its particular network and protection timings do not determine the transient for a grounding-device bypass. Use it as a reason to preserve the transition state, not as a source of a universal voltage multiplier.

Check the external devices across their own terminals

List neutral-connected sensors, resistor insulation, bypass contacts, arresters and leads by their two physical terminals. Compare each device’s applicable voltage and current duty with that specific differential waveform. A neutral-to-earth plot cannot establish stress across an open bypass contact unless the other side’s potential is also known.

Recalculate current when the neutral device is bypassed

Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].

Assume a purely resistive phase-basis equivalent with V₀ = 100 V RMS, transformer Z₀ = 1 Ω, and neutral resistance changing from 1 Ω to 0.10 Ω. I₀ rises from 100/(1 + 3) = 25 A to 100/(1 + 0.30) = 76.92 A. Neutral-to-local-ground voltage falls from 75 V to 23.08 V while winding current rises. Assess the bypass transient separately.

References

  1. D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
  2. IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.