A grounding transformer’s delta winding can carry zero-sequence circulating current while its external terminals are unloaded. The closure joint carries that current. Include its resistance and local heat capacity in the assessment of continuous unbalance and short-time fault duty. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
First identify the complete loop: three winding branches, their series connections and the closure. Record resistance at a common temperature. Measuring a convenient pair of delta terminals without interpreting the parallel paths may not yield the resistance of the closure being investigated.

Retain the induced-voltage sum
An elementary loop model gives Iδ = EΣ/(RΣ + jωLloop). Iδ is the circulating-current RMS phasor in amperes, EΣ is the signed sum of induced loop voltages in volts, RΣ is total loop resistance in ohms, Lloop is effective loop leakage inductance in henries and ω is angular frequency in radians per second.
The sign convention must follow the actual closed path. Positive-sequence induced voltages of a symmetrical delta sum to zero around the loop, while eligible zero-sequence induced components can drive circulation. In the full transformer, the induced voltages themselves respond to magnetic balance, so holding EΣ constant is a defined sensitivity case rather than a complete operating prediction.
Separate two resistance sensitivities
| Assumed case | Effect of higher closure resistance | Interpretation limit |
|---|---|---|
| Circulating current held at the assessed duty | Joint heat rises as |Iδ|²Rjoint | Requires the system and magnetic model to support that current |
| Induced loop voltage held constant | Loop current changes with total impedance | Does not include all transformer magnetic feedback |
| Actual connected unit | Current, flux and loss distribution must be solved together | Neither simplified case alone settles operation |
For an illustrative fixed-current example, a 100 A RMS circulating current through a 1 milliohm joint produces 10 W; through a 5 milliohm joint it produces 50 W. Resistances are 0.001 and 0.005 ohm. These values describe arithmetic sensitivity, not measured joint condition or an acceptance threshold.
Under a fixed voltage and a purely resistive total loop, increasing resistance reduces current. The joint’s share of heating depends on its fraction of that total resistance and can vary non-monotonically over a broad change. Saying that resistance increased therefore current and total heat increased would be internally inconsistent with that assumed circuit.
Locate concentrated heat in the closure joint
A closure joint may have little thermal mass and a less favorable cooling path than the conductor around it. A modest fraction of total loss can create a high local temperature. Include contact geometry, connection pressure, material condition and heat transfer when interpreting resistance and thermal evidence.
For continuous unbalanced service, retain the actual circulating-current spectrum and temperature. For a brief fault, retain the event waveform and initial joint state. Measurements should refer to the same physical joint and common resistance reference temperature so an apparent change is not merely temperature correction.
Track the closure joint’s resistance, corresponding circulating current and local heat increment together. Separate the joint contribution from total copper loss so the design review can identify the actual thermal bottleneck.
Locate the joint energy concentration
Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].
For the assumed 100 A RMS circulation, increasing joint resistance from 1 mΩ to 5 mΩ raises local loss from 10 W to 50 W. Over an assumed 5 s fault, joint energy rises from 50 J to 250 J. If the joint-region heat capacity is assumed 100 J/K, the adiabatic rises are 0.5 K and 2.5 K. Investigate that local interface rather than using total winding loss to judge its temperature.
References
- D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
- IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.

