Follow a spacer-pitch revision through conductor support, oil passages and local insulation geometry. An unchanged winding envelope can contain a different unsupported span, contact pattern and flow boundary.

Measure the geometry that each discipline uses
Record spacer width, position, contact area, unsupported conductor length and duct openings in the assembled condition. Nominal centre-to-centre pitch alone does not identify those interfaces. Preserve the measured pattern and tooling identity in the configuration record [1].
Check the complete circumference or relevant winding path, including joints and locally interrupted patterns. A regular pitch measured over an accessible sector cannot represent a missing support beside a lead exit. Relate the measurements to the actual tooling revision and winding build.
Use a span calculation as a sensitivity screen
All numerical inputs in this comparison are assumptions. In an illustrative simply supported beam under the same uniform transverse load per unit length, bending moment scales with unsupported span squared and elastic deflection with span to the fourth power. If the span rises from 20 to 24 mm, those ratios are 1.2² = 1.44 and 1.2⁴ = 2.0736. This is not a transformer short-circuit calculation: actual conductors, support compliance, contact and load distribution require their own model.
| Geometry consequence | Analysis input to update | Evidence relevant to validation |
|---|---|---|
| Changed free conductor span | Support positions, stiffness and force distribution | Representative mechanical response and dimensional stability |
| Changed duct opening or blockage | Flow network and local heat-transfer geometry | Relevant flow/thermal observations under represented cooling duty |
| Changed solid/liquid interfaces | Actual local electric-field geometry | Appropriate dielectric evidence for the revised construction |
| Changed spacer contact area | Compression and retained assembly dimensions | Conditioned material and assembled contact measurements |
Keep the three validation questions separate
A favourable temperature rise cannot demonstrate sufficient mechanical restraint. A mechanically stable build does not establish an unchanged dielectric field. Likewise, an acceptable overall flow rate can coexist with a local passage that receives less flow. Select evidence for each consequential dependency rather than treating one whole-transformer result as universal clearance.
Define the inheritance boundary on the revised drawing
Mark the changed spacer pattern and every test or calculation that depends on it. Preserve old evidence for genuinely represented features with a written reason, including any unchanged regions. Where a simplified model screens a sensitivity, retain its boundary conditions and identify the confirming evidence still needed. [1]
Use the span sensitivity to select the confirming check
Assumptions for the beam screen: unchanged uniform transverse load, elastic modulus, conductor section and ideal simple supports. Increasing free span from 20 to 24 mm raises maximum moment by 44% and elastic deflection by 107.36%. An assumed 0.50 mm original deflection would become 1.0368 mm. Against an assumed 1.0 mm clearance budget, that leaves −0.0368 mm. Recheck the real load and support compliance [2] before inheriting the old clearance assessment, and identify the revised spacer arrangement in the controlled build [1].
Release the revision against the measured assembled spacer pattern and its mechanical, oil-flow and field evidence. Reconcile the build with the tooling revision so local missing supports or flow changes are captured before inheriting earlier qualification.
References
- NASA, NASA Systems Engineering Handbook, section 6.5, Configuration Management, official online text.
- R. T. Barrett, Fastener Design Manual, NASA Reference Publication 1228, 1990.