Winding Frictional Damping: Calculate the Slip Energy before Assigning a Damping Ratio

  • Chenfan Power

Calculate frictional damping from contact slip and dissipated work. A clamped interface can transmit substantial shear while remaining stuck and dissipating almost no frictional energy. Resolve that state before assigning a damping ratio to the winding response.

Resolve normal contact pressure, tangential compliance and slip together. Then calculate the work dissipated over the actual fault response. The resulting energy is a stronger validation target than a convenient modal damping coefficient.

Stick, local slip and gross sliding are different states

Specify a compressive normal-contact law and a tangential stick/slip law. For the lumped comparison below, use a linear tangential spring in series with a Coulomb slider; identify both its stiffness and limiting force.

At a contact point, stick requires tangential traction below the current slip threshold. The threshold generally depends on normal pressure. A distributed interface can contain sticking and slipping regions simultaneously, producing local slip without visible sliding of the entire spacer or conductor pack.

Use a tangential force limit F_c = μN for a simple lumped contact with zero cohesion. Here N is the compressive normal force. If contact opens, this frictional capacity disappears. Keeping F_c fixed while N changes during a fault produces incorrect slip work, even if the displacement plot looks smooth.

An elastic-slider benchmark makes the energy test exact

Consider one Jenkins element: a tangential spring of stiffness k_t in series with an ideal Coulomb slider. Let the imposed relative displacement cycle between −A and +A after a steady hysteresis loop is established. The elastic slip threshold is:

u_y = F_c/k_t.

For A ≤ u_y, the element remains elastic and the cycle loss is zero. For A > u_y, the loop area is:

ΔW = 4F_c(A − F_c/k_t).

Assumption: Assume k_t = 10 MN/m, N = 500 N and μ = 0.20. Then F_c is 100 N and u_y is 10 μm. A 5 μm cycle dissipates zero energy; a 20 μm cycle dissipates 4 mJ. Both cases have nonzero contact stiffness. Only the second includes slider movement.

Now double N to 1,000 N while keeping k_t and μ fixed. The threshold becomes 20 μm. At A = 20 μm, the ideal element just reaches the slip limit and has zero loop area. Increasing clamp force has removed the slip that previously dissipated 4 mJ. At A = 40 μm, the new loop loss is 16 mJ.

This benchmark establishes why frictional damping is not a monotonic function of clamping pressure. Pressure changes the sliding threshold; the response amplitude determines how much of the cycle actually slides.

Original elastic-slider hysteresis loop: a 20 μm cycle dissipates 4 mJ at 100 N slip force, but zero at a 200 N limit.
Original elastic-slider hysteresis loop: a 20 μm cycle dissipates 4 mJ at 100 N slip force, but zero at a 200 N limit.

A viscous equivalent belongs to one operating point

For a sinusoidal displacement of amplitude A and angular frequency ω, a viscous damper dissipates πcωA² per cycle. Matching this to the 4 mJ benchmark at 100 Hz and A = 20 μm gives an equivalent c of about 5,066 N·s/m.

That coefficient is an energy equivalence at one amplitude and frequency. Apply it at 5 μm and it predicts positive dissipation, whereas the elastic-slider benchmark predicts none. Apply it after contact pressure changes and it retains the old loss mechanism. A constant viscous approximation is useful only over an established range where it reproduces the relevant work and response.

A short-circuit pulse is also not necessarily a completed steady cycle. Integrate the actual frictional power during the event and compare it with the changing kinetic and elastic energies. Use the closed-loop calculation as a unit test of the contact implementation, rather than multiplying its cycle loss by an assumed number of oscillations.

Identify the contact law with the assembled condition

Test relative displacement, tangential force and normal load on the interface that carries the mechanical load. Keep surface condition, oil exposure, temperature and loading direction representative. Repeat at several normal pressures, motion amplitudes and slip velocities. The force-displacement loop identifies energy directly; a measured force plateau alone does not identify the tangential stiffness.

For the winding analysis, report which regions stay stuck, which develop local slip, and which undergo gross sliding. Compare the integrated frictional loss with the measured force-motion work and inspect the energy balance for artificial numerical damping.

Tie damping to the identified interface, its slip history and its energy balance. Check the displacement response against that mechanism: the same interface can dissipate energy at one amplitude and remain effectively elastic at another.

IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]

Retained preload and joint stiffness determine how a clamped load path responds and when compression is relieved. [2]