Map each cable junction and returning reflection in a branched collector network. Waves split at the junctions and return from different terminations on different schedules, creating overlapping excitation at the breaker and transformer.
Popov’s experimental work demonstrates the need to retain propagation when interpreting transformer terminal and winding response. A branched network requires additional junction and termination detail beyond an equivalent unbranched cable. [1]

Calculate the first junction boundary
Before later reflections return, the outgoing branches present their characteristic impedances at the junction. For an illustrative incoming line of 40 Ω feeding two outgoing 40 Ω lines, the initial parallel load is 20 Ω. The voltage reflection coefficient is (20 − 40)/(20 + 40) = −1/3 under the assumed lossless, uncoupled boundary.
Once waves return from the branch ends, that initial boundary no longer describes the complete junction behavior. Their timing and signs must be carried through the network. Retain chopping, gap recovery and quenching in the breaker representation [2].
Draw a reflection-path record
| Path item | Required data | Wave consequence |
|---|---|---|
| Junction | Connected branch impedances | Initial split and reflection |
| Each branch | Length, propagation and loss | Arrival and return times |
| Each termination | Actual device and switching state | Reflection magnitude and phase |
| Transformer node | Wideband port and protection branches | Local loading of the combined arrivals |
| Breaker node | Gap state and source boundary | Interaction with later interruption events |
Retain the actual branch availability
In the proposed network model, retain an electrically connected unloaded branch as a possible wave path. Model an isolated branch only through its verified remaining coupling. These are topology distinctions; Popov’s unbranched prototype is not validation of this collector junction.
Include phase coupling and cable geometry where required by the model’s frequency range. The scalar example above does not establish a three-phase collector’s complete modal impedance.
Test the proposed simplification
Compare the detailed network with the reduced total-capacitance model under the same source, breaker and transformer boundaries. Check first-wave slope, peak, oscillation bands and later arrival timing.
Use relevant topology cases, not just the one case used to choose an equivalent capacitance. A reduction matching one terminal peak can miss a delayed wave that changes reignition or internal winding excitation.
Validate the reduced network against the detailed topology over the required response band and switching cases. Retain the branches, or an equivalent that preserves them, wherever arrival sequence changes reignition or winding excitation. Document the remaining waveform error alongside the simplification.
References
- M. Popov, R. P. P. Smeets, L. van der Sluis, H. de Herdt and J. Declercq, Experimental and Theoretical Analysis of Vacuum Circuit Breaker Prestrike Effect on a Transformer, IEEE Transactions on Power Delivery 24, 2009. DOI: 10.1109/TPWRD.2009.2013383.
- B. Kondala Rao and G. Gajjar, Development and Application of Vacuum Circuit Breaker Model in Electromagnetic Transient Simulation, IEEE, 2006. DOI: 10.1109/POWERI.2006.1632503.