DC Bias or Inrush? Read the Harmonics in Their Event Context

  • Chenfan Power

Energisation inrush and sustained DC bias can both create unequal half-cycle magnetic excursions and second-harmonic current. Distinguish them through the onset, duration and recovery recorded around the event. [1]

During energization, switching angle and remanent flux influence the initial flux trajectory. With sustained DC bias, a continuing current input shifts the magnetic operating condition while AC excitation remains present. The two mechanisms can overlap if a transformer is energized during a DC-current event.

DC Bias or Inrush? Read the Harmonics in Their Event Context: technical review table
Put breaker timing beside the current record

Put breaker timing beside the current record

Establish whether the affected transformer actually changed its energized state. An inrush explanation requires the relevant switching event, including a nearby transformer energization if sympathetic interaction is being considered. A remote breaker timestamp without an identified electrical path is insufficient.

For the sustained-bias explanation, retain an independently measured quasi-DC channel and its conversion to the affected winding. A conventional current transformer may reveal asymmetric AC current but does not provide a valid steady DC measurement.

EvidenceInrush explanationSustained-bias explanation
Relevant energization timeExplains the onset of the initial transientNot required for an already energized unit
Independent neutral or winding DCCheck for a simultaneous separate bias sourceSupports continuing excitation when the path is established
Successive waveform windowsInitial offset generally evolves after switchingAsymmetry can track a persisting DC input
Harmonic contentConsistent with nonlinear excitation, not unique proofConsistent with nonlinear excitation, not unique proof
Removal of the candidate inputFollow post-energization evolutionFollow changes after the DC input subsides

Compare the complete event evolution

Plot several intervals before and after the onset using the same polarity, sampling treatment and harmonic extraction. Preserve positive and negative current peaks, the fundamental component and the independent DC trace. Label any sensor clipping or missing samples. [2]

A harmonic percentage can rise because its numerator increases or because the fundamental denominator falls. Review both component magnitudes. Short analysis windows during rapid waveform evolution can also produce results that are not directly comparable with a steady-state harmonic estimate.

Do not assign a universal decay time to inrush. Circuit resistance, source conditions, core state and interaction with connected equipment affect its evolution. Persistence is stronger evidence when the alternative mechanisms and instrument behavior have also been examined.

Allow a mixed or unresolved diagnosis

If an energization timestamp and independently supported DC current coincide, test both inputs in the model. Removing either one merely to obtain a simpler label may lose the mechanism producing the observed peaks.

Use the primary waveform and event timing to test each explanation against onset, duration and recovery. Record the observations that support or contradict it; a relay harmonic flag provides a starting point for that investigation. [3]

References

  1. B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
  2. R. L. Bailey and coauthors, Modelling geomagnetically induced currents in midlatitude Central Europe using a thin-sheet approach, Annales Geophysicae 35, 2017. DOI: 10.5194/angeo-35-751-2017.
  3. NERC, Transformer Thermal Impact Assessment White Paper, Project 2013-03 Geomagnetic Disturbance Mitigation, October 2017.