Trace the source supplying observed feeder voltage after a conductor opens. Identify whether a connected inverter contributes current or energy through the remaining network. The NREL research distinguishes power-export and local voltage/frequency-control objectives; actual control and limiting determine the applicable response [1].

Mark every energized source
Draw the remaining utility phases, transformer windings, inverter connection and loads. Identify the opened element and each meter. The SEL study concerns specified fuse-protected transformer circuits [2]; an inverter adds a source and controls outside those passive-load cases.
Separate energy transfer from a coupled or capacitively supported voltage with little available current. Use terminal current and directional power on a defined sign convention alongside voltage. A normal-looking voltage phasor does not establish the same supply stiffness or fault contribution as the intact source.
| Inverter state to represent | Model evidence | Observation to retain |
|---|---|---|
| Connected power export | Applicable synchronization and power-control model | Voltage/current at the inverter and transformer boundary |
| Current-limited response | Limit implementation and relevant control transitions | Clipping, power change and sequence response |
| Cessation or disconnection | Actual configured logic and timing evidence | Loss of contribution and remaining coupled voltages |
| Intentionally supported island | Its documented source and protection arrangement | Defined island boundary and represented operating conditions |
Use the actual controller capability
Grid-following and grid-forming labels do not supply a complete abnormal-event model. The NREL research models distinguish synchronization/power control from local voltage/frequency control and implement current limiting. The paper also states that generic models do not replace plant-specific study models. [1]
Confirm whether the chosen representation covers unbalanced conditions, limiting, protection and transitions relevant to this event. A positive-sequence-only or ideal-source model can omit precisely the response that determines apparent voltage recovery. Do not assume a grid-following device can sustain an unsupported island.
Compare identical physical openings
As an event-study procedure, hold the opened conductor and transformer topology fixed while changing the represented inverter state. Retain the same load and source assumptions, then identify observations attributable to the added source. Preserve any coupled changes in control settings or load behaviour.
Check measurements on both sides of the transformer and at the inverter boundary where available. A recovered downstream voltage and an abnormal upstream current can coexist. Avoid using one measurement location to certify the condition of another.
For each modeled state, identify the source energizing each region, its current and power contribution, and the controller transition that changes the waveform. Attach the unresolved paths and model limits to this map before it is used in an islanding or restoration assessment.
References
- R. W. Kenyon, A. Sajadi, A. Hoke and B.-M. Hodge, Open-Source PSCAD Grid-Following and Grid-Forming Inverters and a Benchmark for Zero-Inertia Power System Simulations, NREL/CP-5D00-78402, April 2021.
- J. LaBlanc, Y. Shah and J. Aultman, Schweitzer Engineering Laboratories, Revisiting Open-Phase Detection for Fuse-Protected Power Transformers, 2024.