Load damping depends on the load characteristic, connection point and nonlinear circuit state. Quantify the energy dissipated by the proposed load and evaluate its effect on the response across the relevant initial histories. [1] [2]
Jacobson’s case discussion distinguishes the burden needed to prevent a response from that needed to extinguish an established one, and notes thermal constraints on the damping location. Those case values cannot be transferred into a general minimum-load percentage.

Define what load means at the relevant port
Retain real power, reactive behavior and voltage dependence. A nominal kVA value alone does not establish damping. A passive resistance dissipates power according to the voltage across it; a controlled or nonlinear load may have a different dynamic characteristic. [1]
Model the actual winding and connection through which the load acts. A load at a secondary port can influence the primary circuit through the transformer’s coupled response, but the effect depends on that connection and the state being studied.
Map prevention and extinction separately
| Assessment | Starting state | Question |
|---|---|---|
| Prevention | Credible pre-switch charge and magnetic history | Does the loaded circuit enter an abnormal state? |
| Extinction | Supported established abnormal response | Does the proposed load move it to an acceptable response? |
| Parameter sensitivity | Required network and model variations | How consistent is the observed boundary? |
| Thermal feasibility | Normal and required mitigation duty | Can the load and supplying winding carry the exposure? |
Scan the load with several credible initial states. A normal zero-state run does not prove prevention for a trapped-charge case. Conversely, a load that stops one established mode may not address another accessible mode. [1]
Record how the load is represented during transitions. A permanently connected load and a detected, switched load have different timing, reliability and initial-duty questions. This comparison defines study cases, not field connection instructions.
Check energy removal and thermal consequence
Compare average source input and dissipation over a suitable multi-cycle interval. Identify the port where the added load removes energy and whether that port sees the governing oscillatory voltage. [1]
Retain continuous losses, transient absorbed energy and the duty imposed on the transformer winding. A model can suppress an oscillation with a resistance whose thermal burden is not physically supported. That is a mathematical result, not an implementable mitigation.
Include credible tolerances and loss-model uncertainty when deciding the boundary. If the outcome changes sharply near one assumed load, report the transition region rather than one falsely precise threshold.
Specify load characteristic, location, operating state and thermal capability for the chosen damping arrangement. Verify both its effect on the response and its ability to sustain the assigned duty.
References
- P. Ferracci, Schneider Electric, Ferroresonance, Cahier Technique No. 190, March 1998.
- D. A. N. Jacobson, Examples of Ferroresonance in a High Voltage Power System, IEEE PES General Meeting, 2003. DOI: 10.1109/PES.2003.1270499.

