Configuration-Specific Data for Reconnectable Transformers

  • Chenfan Power

Give each achievable reconnection mode one coherent data row. Voltage, current and cooling rating must describe the same physical assembly and operating state. Keep that configuration schedule aligned with the nameplate and controller mapping. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Configuration-Specific Data for Reconnectable Transformers: technical review table
Give each configuration its own data row

Give each configuration its own data row

Assign a mode identifier linked to the approved connection and indication. Put the related voltage, power, current, cooling and impedance data together. State the side and electrical base for each quantity, and distinguish rated conditions from limits or optional configurations.

Illustrative modeThree-phase powerRelevant side voltageDerived side currentAssociated evidence
A10 MVA10 kV line-to-line577 AMode-A connection, cooling and impedance records
B10 MVA20 kV line-to-line289 AMode-B connection, cooling and impedance records

For this hypothetical balanced example, I = S/(√3VLL). The currents are about 577.35 A and 288.68 A. The example is a data-structure illustration, not an actual product rating. Selecting 20 kV from row B and 577 A from row A would imply 20 MVA under that formula, although neither row declares that configuration.

Attach qualifiers where they belong

Associate impedance with its mode, tap, power/voltage base and applicable test condition. Associate thermal rating with the actual cooling deployment, ambient boundary and any defined duty duration. Preserve winding connection, phase displacement and neutral information for each configuration where they differ.

Do not put a qualifier only in a remote footnote if it changes the meaning of a frequently used row. The operational identifier must let an engineer retrieve the matching connection drawing, model and protection information without combining fields from different modes.

Distinguish available options from installed states

A catalog option is not necessarily present on the delivered unit. Record which configurations the particular serial-numbered assembly supports, including necessary cooler banks, reconnection parts and adapters. A listed voltage mode may require a different accessory package or have a different supported thermal boundary.

Keep the nameplate, configuration schedule and technical package synchronized after an approved change. A corrected table in a digital file does not resolve an outdated physical label or controller mapping.

Check a selected mode from terminal voltage through current, cooling and connection data in the same row. A complete configuration record lets the buyer identify the duty the installed transformer actually supports.

Check the lowest-voltage current bottleneck

Keep the approved mode drawing, identifier and data revision on one configuration baseline [2].

Assume a 10 MVA three-phase mode at 10 kV and another at 20 kV line-to-line. Line currents are S/(√3V), or 577.4 A and 288.7 A. An assumed 500 A link limit restricts the 10 kV mode to √3 × 10 kV × 500 A = 8.66 MVA. Carry that local limit into the configuration sheet.

References

  1. U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.
  2. NASA, NASA Systems Engineering Handbook, section 6.5, Configuration Management, official online text.