Map each permitted multiwinding load partition to its winding currents, losses and cooling demand. Extending a thermal trial to another split requires the corresponding loss and temperature evidence. IEC 60076-2 covers temperature-rise tests for liquid-immersed transformers [1]; its public scope supplies no partition-specific extrapolation rule.
The unresolved quantity is often a particular winding’s heating and cooling duty. The report should identify the load partition represented by the trial, rather than describe the transformer as thermally qualified without stating that operating condition.

Translate each operating case into winding-specific inputs
List voltage, current, tap position, power factor and relevant harmonic content for each winding in the intended operating case. Use a consistent system model so the currents and powers satisfy the electrical connections. Winding loss allocations cannot be selected independently merely to make a convenient thermal total.
Evaluate conductor and additional winding losses, local lead or structural heating and cooling-path demand. A change in one secondary’s load can affect several heat sources and oil-flow interactions. Similar total losses do not establish similar local winding temperatures.
Label what each trial actually represents
| Intended service case | Inputs to identify | Evidence the trial must connect to that case |
|---|---|---|
| Secondary1-dominant loading | Actual currents in all connected windings and the resulting loss map | Heating and measurements representative of secondary1 and its cooling path |
| Secondary2-dominant loading | Changed current split, tap duty and local additional losses | Evidence that secondary2 duty is covered rather than inferred from secondary1 |
| Simultaneous high secondary loading | Electrically consistent combined duty and shared oil-circuit demand | Thermal interaction represented in the approved test or validated analysis |
| Unbalanced permitted load division | The allowed current envelope and component limits | A stated bound on cases the measured test does not directly reproduce |
Use the matrix to identify the trial and supporting analysis for each specified load partition. The governing procedure and design review determine the acceptable tests and extrapolations.
Distinguish the heat-run arrangement from service operation
The approved trial may use an excitation arrangement chosen to establish required total heating or particular winding currents. Document that arrangement and the relation between its heat sources and the intended service case. Name any source that is supplied differently or represented through a correction or model.
Compare the relevant winding averages and local sensors under that defined arrangement. A satisfactory oil-temperature result alone does not establish an untested secondary winding’s local thermal duty.
Compare equal total loss under two load partitions
Assume a single-phase ideal 10 kV/1 kV/1 kV transformer with zero primary resistance and core loss, 0.8 Ω resistance in each secondary, unity-power-factor resistive loads and negligible leakage. Case A secondary currents are 100 A and 50 A; case B swaps them. Induced secondary voltages remain 1 kV, so loaded terminal voltages are 920/960 V or 960/920 V. Both cases deliver 140 kW, dissipate 10 kW in secondary copper and draw 15 A at 10 kV; 150 kW input balances load plus copper loss. The secondary losses are 8/2 kW or 2/8 kW [2]. Assume the steady linear thermal relation ΔT₁ = 4P₁ + P₂ and ΔT₂ = P₁ + 3P₂, with P in kW and coefficients in K/kW. Results are 34/14 K for A and 16/26 K for B [3]. A test representing A therefore leaves winding 2’s higher rise in B uncovered. Test that partition or validate its coupled thermal representation before extending coverage; equal total loss alone cannot close it.
References
- IEC, IEC 60076-2:2011, Power transformers — Part 2: Temperature rise for liquid-immersed transformers.
- U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.
- U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.