Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Emergency Mobile Transformers on a Weaker Source

  • Chenfan Power

A weaker source changes a mobile transformer’s energization disturbance, available fault current and interaction with connected loads. Assess voltage recovery, motor and auxiliary starting, and protection sensitivity using the source equivalent at the actual temporary connection. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Emergency Mobile Transformers on a Weaker Source: technical review table
Define source strength at the actual connection

Define source strength at the actual connection

Obtain the relevant source equivalent, voltage-control behavior and available configurations at the mobile connection point. Include the temporary cable path and other transformers. A fault level quoted for a remote bus does not necessarily describe the impedance seen by the mobile unit.

Study questionInputs that change with source strengthResult to examine
EnergizationSource impedance, switching state and transformer magnetic behaviorVoltage and current trajectories, not steady MVA alone
Load pickup or motor responseLoad dynamics, cable impedance and voltage controlVoltage recovery and required load performance
Earth and phase faultsSource paths, grounding and mode-specific impedanceMinimum and maximum relevant fault currents
ProtectionCT coverage, fault quantities and qualified settings reviewSensitivity and security in the temporary configuration
Auxiliary operationStarting profiles and voltage-quality requirementsAchieved cooling and retained protection/control supply

Use a restricted calculation to show the mechanism

In an illustrative single-frequency model, assume an initially unloaded source with E = 1 per unit, source impedance j0.10 per unit and an imposed incremental current −j0.50 per unit. The incremental drop ZΔI is +0.05 per unit, so the terminal voltage becomes 0.95 per unit when other quantities are held fixed. The same current through j0.02 would give a 0.01 per-unit drop.

This phasor example demonstrates impedance sensitivity. It is not an inrush prediction: real energization has a nonlinear magnetic state, asymmetry and time dependence, and the source may have active controls. Those effects require an appropriate dynamic model and relevant evidence.

Check the low-fault-current boundary as well

A weaker source can reduce a fault quantity that an existing protection scheme relied on. Review the selected voltage mode, zero-sequence paths and fault configurations instead of scaling every current from a single short-circuit number. Determine the required protection changes from the station study and the relay’s documented functions.

Compare the supported source configurations and identify the controlling duty: voltage recovery, load demand, auxiliary starting or protection sensitivity. Use that result to qualify the emergency connection and specify any required changes.

Carry source strength into the voltage-recovery study

Keep winding connection and current-compensation assumptions matched when reviewing transformer fault protection [2].

The assumed incremental −j0.50 per-unit current produces 0.05 per-unit drop through j0.10 source impedance and 0.01 through j0.02. On an assumed 10 kV line-to-line base, these are 500 V and 100 V. The fivefold difference justifies separate energization and auxiliary-start simulations for the weaker connection, using its actual nonlinear and controlled-source response.

References

  1. U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.
  2. B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing