A K-rated transformer and a harmonic-mitigating transformer address different objectives. K-rating is associated with capability to withstand specified nonsinusoidal load heating; harmonic-mitigating designs use winding/phase-shift or impedance features to reduce selected harmonic currents in a system. A procurement document should name the required performance and evidence instead of treating the two labels as synonyms.

Withstanding a harmonic load does not remove it
A K-rated design addresses a defined nonsinusoidal heating duty within its stated rating and applicable evaluation method. It does not, by that label alone, cancel the customer's harmonic current or guarantee a specified THD at the utility connection. Ask which K-rating convention and product requirements apply, what operating conditions support the rating, and how neutral duty is declared. Avoid interpreting the numerical K designation as a general percentage improvement in power quality.
Mitigation depends on the connected load arrangement
Phase-shifting transformer arrangements can reduce selected harmonic components at a common upstream point when the supplied load groups have the required phase relationship and sufficiently comparable spectra. Unequal loading or different converter operating modes reduces the expected cancellation. Some designs also use impedance or connection features for particular zero-sequence components. The supplier should identify the harmonics targeted, the measurement point and the load conditions behind the claim rather than promising unspecified “clean power.”
Write separate acceptance requirements for heat and distortion
A project can require both thermal capability and reduced upstream distortion, but these need separate evidence. The thermal assessment uses winding losses, ambient and cooling under the stated spectrum. The power-quality assessment uses the complete network, load diversity and the agreed measurement method. Request both where needed, and compare offers against the same conditions. Neither a harmonic-mitigation label nor a K-rating should be treated as a substitute for the other requirement.
Technical reference framework
[1] IEEE C57.110-2018 — Transformer capability with nonsinusoidal load currents.
[2] IEC 60076-1:2011 — Power transformers, General.