Chenfan Electric
EN
Send drawing

ARTICLETechnical article

GSU Tertiary Duty During a Synchronizing Error

  • Chenfan Power

A synchronizing error creates a voltage difference between the generator and the system at closing. Its current distribution follows the network and the multiwinding transformer’s impedance relationships. There is no universal percentage of the main current that can be assigned to the tertiary. Keep the selected winding arrangement within the general power-transformer specification framework [1].

Represent the closing mismatch as ΔV = Vg − Vs with both phasors referred to the same side and phase sequence. Even equal voltage magnitudes create a mismatch when the phase angles differ. For equal magnitude V and angle difference δ, |ΔV| = 2V|sin(δ/2)|. Here V is phase RMS voltage and δ is the electrical angle.

GSU Tertiary Duty During a Synchronizing Error: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

List what can actually drive the tertiary

ContributionPath neededData for calculation
Balanced closing mismatchCoupling through all connected winding circuitsMultiwinding leakage impedances and terminal networks
Tertiary external loadClosed tertiary feederLoad model and source state
Zero-sequence componentConnection and grounding that support the componentSequence network and winding configuration
Internal delta circulationClosed delta pathRelevant induced voltage and winding impedance

A balanced fundamental-frequency mismatch should not automatically be labelled a zero-sequence event. Zero sequence requires its own source and return path. Conversely, a closed delta can carry internal circulating current that is absent from its external line-current measurement.

Use the right transformer model

A two-winding equivalent can show the main mismatch current but cannot reliably partition a three-winding event. Obtain the winding-pair impedances, connection and terminal load states. Use a consistent reference base and check whether the derived equivalent represents the supplied impedance data.

The formula for ΔV is a screening relation. Current peaks also depend on closing instant, resistance, network dynamics and saturation. A mechanical-duty calculation needs phase-current peaks and spatial force distribution rather than only the mismatch’s RMS magnitude.

Screen the closing mismatch on one voltage base

Assume equal 10 kV phase-RMS sources with 10° closing-angle mismatch and total series reactance 2 Ω at 50 Hz. Mismatch voltage is 2 × 10 × sin 5° = 1.743 kV; the simple symmetrical current estimate is 1743/2 = 872 A. At 5° mismatch it is 436 A, about half. These values only screen the main path. Use the three-winding network to allocate tertiary duty and a transient model for peaks; the screen does not establish a permitted synchronizing angle.

Preserve the error case without endorsing it

Define voltage difference, angle error, slip frequency and breaker closing scatter as study inputs. Record tertiary load and earthing in the same case file. Compare its current and thermal burden with the tertiary’s actual design data.

The review should distinguish protection prevention of an erroneous close from the equipment’s specified withstand case. Calculating the latter is not permission to synchronize outside the plant’s approved conditions.

Verify the selected terminal ratio with a test method matched to the winding connection [2].

References

  1. IEC, IEC 60076-1:2011, Power transformers – Part 1: General.
  2. Ohlen, M., and Werelius, P., A Guide to Transformer Ratio Measurements, Megger Sweden, 2010-01-18, Definitions and TTR measurements.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing