M-6 technical data sheet
JFE Steel · 0.35 mm · Published core loss and magnetic properties
Grade comparison and supply
50 Hz · 0.35 mm
Find a Chinese alternative
Share your drawing or core loss target to check available grades.
Quote alternative60 Hz · 0.35 mm
Find a Chinese alternative
Share your drawing or core loss target to check available grades.
Quote alternativeGrade summary
JFE Steel · 0.35 mm · 50 / 60 Hz
10 published records · Published flux density range 1.5–1.7 T
| Metric | Test point | Value | Source |
|---|---|---|---|
| Specific core loss | 50 Hz · 1.5 T (J) | 1.11 W/kgGuaranteed maximum | PDF page 10 |
| Specific core loss | 50 Hz · 1.7 T (J) | 1.57 W/kgGuaranteed maximum | PDF page 10 |
| Specific core loss | 50 Hz · 1.5 T (J) | 1.02 W/kgTypical | PDF page 11 |
| Specific core loss | 50 Hz · 1.7 T (J) | 1.47 W/kgTypical | PDF page 11 |
| Specific core loss | 60 Hz · 1.5 T (J) | 1.46 W/kgGuaranteed maximum | PDF page 10 |
| Specific core loss | 60 Hz · 1.7 T (J) | 2.07 W/kgGuaranteed maximum | PDF page 10 |
| Specific core loss | 60 Hz · 1.5 T (J) | 1.34 W/kgTypical | PDF page 11 |
| Specific core loss | 60 Hz · 1.7 T (J) | 1.92 W/kgTypical | PDF page 11 |
| Magnetic polarization | 800 A/m | 1.80 TGuaranteed minimum | PDF page 10 |
| Magnetic polarization | 800 A/m | 1.83 TTypical | PDF page 11 |
Download the PDF for the full published tables, test conditions and source references.