H-1 CARLITE technical data sheet

Cleveland-Cliffs · 0.27 mm · Published core loss and magnetic properties

Grade comparison and supply

50 Hz · 0.27 mm

Find a Chinese alternative

Share your drawing or core loss target to check available grades.

Quote alternative

60 Hz · 0.27 mm

Find a Chinese alternative

Share your drawing or core loss target to check available grades.

Quote alternative

Grade summary

Cleveland-Cliffs · 0.27 mm · 50 / 60 Hz

162 published records · Published flux density range 0.1–1.9 T

MetricTest pointValueSource
Specific core loss 50 Hz · 1.5 T (B) 0.73 W/kgGuaranteed maximum PDF page 3
Specific core loss 50 Hz · 1.7 T (B) 1.00 W/kgGuaranteed maximum PDF page 3
Specific core loss 50 Hz · 0.1 T (B) 0.00383 W/kgTypical PDF page 12
Specific core loss 50 Hz · 0.1 T (B) 0.00362 W/kgTypical PDF page 10
Specific core loss 50 Hz · 0.2 T (B) 0.01439 W/kgTypical PDF page 12
Specific core loss 50 Hz · 0.2 T (B) 0.01390 W/kgTypical PDF page 10
Specific core loss 50 Hz · 0.3 T (B) 0.0317 W/kgTypical PDF page 12
Specific core loss 50 Hz · 0.3 T (B) 0.0308 W/kgTypical PDF page 10
Specific core loss 50 Hz · 0.4 T (B) 0.0551 W/kgTypical PDF page 12
Specific core loss 50 Hz · 0.4 T (B) 0.0539 W/kgTypical PDF page 10

Download the PDF for the full published tables, test conditions and source references.